DN 1 ... DN 1000 (1/25 ... 40") with PROFIBUS PA / FOUNDATION Fieldbus
S4 transmitter (wall mount housing)
6
1
U+
3
2S
2
7
8
9
10
11 12
SE 3
2S
2
SE 3
U+
2
Flowmeter sensor
Fig. 28:
Connection diagram: transmitter S4 with PROFIBUS PA / FOUNDATION Fieldbus
1
Functional ground (busbar)
2
Contact output (see chapter "connection examples for
peripherals" in the operating instructions and/or data sheet)
3
Digital communication
3a: PROFIBUS PA design accord. to IEC 61158-2 (Profile 3.0)
3a:
U = 9 ... 32 V, I = 10 mA (normal operation)
3a: U = 9 ... 32 V,
I = 13 mA (in the event of error/FDE)
3a:
Terminals: 97/98, PA+/PA-
3a:
(see chapter "connection via M12 plug" in the operating
3a:
instructions and/or data sheet)
3b: FOUNDATION Fieldbus design according to IEC 61158-2
3a:
U = 9 ... 32 V, I = 10 mA (normal operation)
3a: U = 9 ... 32 V,
I = 13 mA (in the event of error/FDE)
3a:
Terminals: 97/98, FF+/FF-
3a:
(see chapter "connection via M12 plug" in the operating
3a:
instructions and/or data sheet)
3c: Bus termination with installed bus termination
3a:
components with hook switches closed
4
Magnet coil cable:
2
shielded 2 x 1 mm
CE Typ 227 TEC 74
ABB order no. D173D147U01, 10 m included in shipment,
standard
Comment:
We recommend that shielded output cables be used with the shields connected to the functional ground at one end.
Important
If the flowmeter sensor is equipped with a preamplifier for low conductivity or in meter size DN 1 ... DN 8
(1/25 ... 5/16"), the shieldings of the signal wires must be connected to terminals U+ and U- on both the flowmeter
sensor and the transmitter.
D184B141U03
6
U-
1
1S
3 16
10 10 13
14
15
M3
SE
1
1S 3A 16
M1
16
M3
M1
SE
1
U- 3A 16
3c
FF+
FF-
PA+
PA-
41 42
97
1
2
3
1
5
Supply power
Low voltage: 100 ... 230 V AC, terminals L, N,
Low voltage: 20.4 ...26.4 V AC;
Low voltage:
Low voltage:
Frequency: 47 Hz ≤ f ≤ 53 Hz; 50 Hz supply power
Frequency:
6
Shielded signal cable:
Power supply for flowmeter sensor with preamplifier
Terminals U+, U- instead of 2S and 1S in standard unit
7
Steel shielding
8
Aluminum foil
9
Yellow
10 Shield
11 Blue
12 Red
13 white
14 Shielded signal cable: ABB order no. D173D025U01,
10 m, included in shipment
15 Without preamplifier
16 With preamplifier (always with DN 1 ... DN 8 [1/25 ... 5/16"])
FSM4000
Electrical connection
3b
3a
1
2- 1+
98
M3
M1
N
4
1
20.4 ... 31.2 V DC
Terminals 1+, 2-,
56 Hz ≤ f ≤ 64 Hz; 60 Hz supply power
1
1
L
5
G00597
EN - 25