Temperature Selection; Domestic Water Mixing - Honeywell MX Serie Manual Del Usuario

Ocultar thumbs Ver también para MX Serie:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

Replacement Parts
Product
Number
MX050-RP
1/2 inch Recirculation Adapter
MX100-RP
1 inch Gasket Kit for MX Series mixing
valves
MX125-RP
1 1/4 inch Gasket Kit for MX Series mixing
valves
MX150-RP
1 1/2 inch Gasket Kit for MX mixing valves
MX200-RP
2 inch Gasket Kit for MX mixing valves
MX250-RP
2 1/2 inch Gasket Kit for MX mixing valves
MX300-RP
3 inch Gasket Kit for MX mixing valves
OPERATION
Automatic operation is provided by the thermostatic
element. Element will control hot and cold supply based on
valve setting. If cold water is shut off, valve reduces mixed
flow in seconds (speed/residual flow rates vary by size).
CAUTION
Do not override calibration. Test temperature with
thermometers.
Service
To remove dirt, flush valve. To remove calcium and lime
deposits, soak valve in vinegar for 24 hours and flush or
contact factory for assistance. Do not attempt to field
repair this calibrated valve.

Temperature Selection

The MX Series Valves are made in ranges: 113°-149° F
(45°-65° C). The factory setting is 130° F (54° C). Change
temperature setting with an Allen wrench, which is
included; 3/16 for MX127LF or a 5/16 for MX128LF,
MX129LF and MX130LF. Punch through the center of the
temperature range label. By turning the screw clockwise,
the mix temperature increases (counterclockwise, it
decreases). Each complete turn with the Allen wrench
changes the temperature as follows: MX127LF (1 in.);
11° F (6° C), MX128LF (1-1/4 in.), MX129LF (1-1/2 in.)
and MX130LF (2 in.), 7° F (4° C). Do not operate valve at
temperatures outside of its calibrated range of 113°-
149° F (45°-65°). Use a thermometer to verify temperature.
TYPICAL INSTALLATION
DIAGRAMS

Domestic Water Mixing

Use when water temperature produced by heater is hotter
than desired at point of use. Many codes require that water
supplied to the system be limited to 120° F (49° C) max.
Description
3
MX SERIES
VALVE
M
C
H
TO DISHWASHER
IF PERMITTED
8
BY CODES
(203)
HEAT TRAP
MAX
WATER
HEATER
Fig. 3. Water heater without recirculation. Dimensions
shown in in. (mm).
PUMP
(1)
T
MX SERIES
VALVE
M
(1)
C
H
TO DISHWASHER
IF PERMITTED
8
BY CODES
(203)
MAX
WATER
HEATER
Fig. 4. Heater with recirculation. Dimensions shown in in.
WATER
USE
FIXTURES
PUMP
T
TO DISHWASHER
IF PERMITTED
BY CODES
FAN COIL
FAN COIL
CONNECTIONS TO
CONNECTIONS
CONVENTIONAL
TO SIDE TAP
WATER HEATER
WATER HEATER
Fig. 5. Water heater is used for domestic water and space
heating. Dimensions shown in in. (mm).
MX SERIES VALVES
(1)
ALLOWABLE
SERVICE
COLD
VALVE
WATER
6
LOCATION
SUPPLY
(152)
V
EXPANSION
TANK
M23686
RECIRCULATION
(1)
HEAT
ALLOWABLE
TRAP
SERVICE
COLD
VALVE
6
WATER
(152)
LOCATION
SUPPLY
V
EXPANSION
TANK
M23687
(mm).
(1)
RECIRCULATION (IF
NO RECIRULATION
IS REQUIRED OMIT
DASHED PIPING)
M
(1)
C
H
8
ALLOWABLE
HEAT
(203)
SERVICE
TRAP
COLD
MAX
VALVE
WATER
6
LOCATION
SUPPLY
(152)
V
WATER
EXPANSION
HEATER
TANK
M23688
38-00035EFS—01

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Mx127lfMx128lfMx129lfMx130lfMx131lfMx132lf ... Mostrar todo

Tabla de contenido