5.9.3
Permitted pipe lengths at parallel air supply and flue tube systems
Permitted pipe lengths when applying Ø80 mm (total of flue pipe and air intake pipe
together).
C13
RHOB12AAV1
100 m
RHOB18AAV1
100 m
RHOB42AAV1
Replacement lengths
Bend 90°
R/D=1
Bend 45°
R/D=1
Knee 90°
R/D=0.5
Knee 45°
R/D=0.5
Calculation example
Pipe
Pipe lengths
Flue gas outlet
L1 + L2 + L3 + 2x2 m
Air supply
L4 + L5 + L6 + 2x2m
Note:
The total pipe length is: sum of the straight pipe lengths + sum of the replacement pipe
lengths of bends/knees amounts to a total of 25 meters. If this value is less than the
maximum permitted pipe length, the flue gas outlet meets the requirements on this point.
C33
C43
C53
100 m
100 m
100 m
100 m
100 m
100 m
60 m
60 m
60 m
60 m
2 m
1 m
4 m
2 m
Pipe length total
13 m
12 m
C83
100 m
100 m
60 m
27