Rotex GW-20 H12 Instrucciones De Instalación página 82

Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 263
5.9.6
Air supply from the facade and a roof outlet with communal
exhaust system
Unit category: C83
An air supply from the facade and a roof outlet with communal exhaust system is
permitted.
IMPORTANT
• The air supply in the facade must be fitted with an inlet
roster (A).
• The communal output system must be fitted with a traction
extractor hood (B).
• If the communal output system is situated in the outdoors,
the output pipe must be double-walled or insulated.
Permitted pipe length
Combustion gas outlet pipe between the unit and the communal output system and
air supply pipe between the unit and the inlet roster together:
RHOB12 & 18AAV1H
100 m
The minimum diameters of the communal output system based on vacuum
Flue tube diameter
Number of units
RHOB12 & 18AAV1H
2
3
4
5
6
7
8
9
10
11
12
IMPORTANT
If you wish to use the unit RHOB42AAV1H in combination
with a C83 smoke gas outlet system, please contact Rotex
Heating Systems GmbH.
Communal combustible gas outlet
The output of the combustion gas outlet can be made in any location on the sloping
roof surface, providing the outlet in the roof surface has the same orientation as the
air supply in the facade. On a flat roof, the outlet of the combustion gas outlet must be
made in the "free" outlet area.
Fit a condense output.
Note
The communal outlet is certified in combination with the unit.
130
150
180
200
220
230
250
270
280
290
300
31

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Gw-20 h18Gw-20 h42Rhob12aav1hRhob18aav1hRhob42aav1h

Tabla de contenido