Main Menu; The Unit´s First Configuration; Configure The Power Limit; Configuring The Country/ Regulation - Ingeteam INGECON SUN 40TL U M480 Manual De Instalacion Y Uso

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

Display control

10.4. Main menu

The main menu contains the following submenus:
Monitoring
This menu includes a series of screens which show the main variables being monitored.
The right-hand screen shows the first one as an example.
Events
This shows the main events such as alarms, warnings and reasons for shutdown.
Start/Stop
Start up and shutdown the inverter manually.
Settings
Modify parameters to adapt the unit to different operational conditions.
Advanced settings
To carry out advanced settings in the inverter. Its access is restricted by the installer
password. Is not user-accessible.
Inverter data
Key information referring to the inverter: serial number, firmware loaded, etc.
To access the various menus and submenus, the desired option must be highlighted over a black background using
the
and
keys and press the
The menu Advanced settings is password restricted. Access to this menu is only allowed to installers
(qualified personnel). The installer password is 3725.
10.5. The unit´s first configuration
The first time that the inverter is powered from the PV array, a series of screens are displayed so as to guide the
inverter´s configuration for proper connection to the electric grid.
Follow the instructions on the display. When selecting the country / regulation, select the country in which the
inverter is going to be installed. If the country is not on the list, select Worldwide and select the applicable
regulation. After selecting the regulation, configure the voltage and frequency.

10.6. Configure the power limit

This option limits, as a percentage of the nominal, the maximum active power that the inverter can inject into the
grid.
To configure the power limit access Main Menu > Settings > Power settings and indicate the percentage of
maximum active power desired.

10.7. Configuring the country/ regulation

Relative to the applicable regulation at the installation, these inverters must work according to a series of
parameters.
To configure the inverter according to the regulation, access Main Menu > Advanced settings > Country regulations.
Select the country where the inverter will be installed. If the country is not on the list, select Worldwide and select
the applicable regulation. After selecting the regulation, configure the voltage and frequency.

10.8. Configuring the Modbus ID

The Modbus ID is the inverter´s identification number within the communications bus. These inverters have two
RS-485 communication lines, so you can configure the Modbus number for two different buses.
To configure it or the Modbus numbers access Main Menu > Settings > Modbus ID.
The COMM 1 ID is the inverter´s ID within the communication bus generated from the RS-485 communication
integrated by default into the unit.
ABO2012IQM01_ - Installation and Operation Manual
1/11/2016
1/11/2016
key to access it.
10:17 AM
10:17 AM
Ingeteam
EN
ES
41