AC connection.
4.
The connection is made via the PCB terminal. Wire the three phases to the terminals marked R (Vac3),
S (Vac1), T (Vac2). Wire the neutral to the terminal marked N and wire the ground conductor to the
terminal marked as PE.
5.
To make the connection, strip an 20 mm section of the cable. Using a tubular terminal is optional.
6.
Screw in the terminal with a torque of 48.68 lb.in (5.5 Nm).
7.
Use a cable tie to secure the cable to the plastic support for this purpose; avoid pulling on the cable.
The AC conduit must remain without voltage while the unit door is open.
Respect the installation of N and PE. Do not interchange with the phases.
Ingeteam accepts no liability for any consequences of incorrect connection.