2.e Water connection
Connect the water heater to the water supply and insert a tap to
intercept the water above the device. From the front, the cold water
input is on the right and the hot water output is on the left.
Insert the filter into the water valve input fitting.
Remove the plastic nut from the hot water output fittin before
connecting it to the water supply.
Ensure that the tubes of you water system are not used to earth your
electrical system or telephone, they are absolutely inappropriate for
performing this task.
In a short amount of time this can damage tubes and the device.
WATER CIRCUIT (Fig.6)
1
Flue gas release hood
2
Flue gas safety device
3
Water limit thermostat
4
Heat exchanger
5
Burner
6
Ignition electrode
7
Thermocouple
8
Pilot burner
9
injector
10
Hot water output
11
Pressure intake
12
Temperature selector
13
Venturi
14
Hydraulic valve
15
Water safety valve
16
Water filter
17
Membrane
18
Cold water input
19
Gas control
20
Gas valve
21
Magnet
22
Gas filter
2.f Disposal of waste product
This B11BS water heater is supplied with a device for releasing flue
gas.
For output of combustion by-products refer to the regulations in force
including any updates. See paragraph 2.a
The gas devices with an attachment for a waste gas flue must be
connected directly to properly working chimney or flue pipe; only if
these devices are not present is it then permitted to release gases di-
rectly outside.
The fitting of devices to a chimney or flue pipe must
occur via a smoke channel. Smoke channels must be connected to
a chimney or a smoke channel in the same or adjacent area to where
the device is installed and must be made of materials resistant to
mechanical strain, heat and the effects of combustion by-products
and their condensation.
The flue gas temperature must always be
above condensation temperature in all points of the smoke channel
regardless of external conditions.
FLUE GAS RELEASE SAFETY DEVICE
The product is equipped with a series of flue gas release safety
devices. The device ensures the correct release of combustion by-
products; the flow of combustible gas to the release conduit and the
smoke channel.
The safety device contains a "thermostat" that is connected to the
thermocouple. The safety device's intervention blocks the thermo-
couple and blocks the flow of gas to the main burner as well as the
pilot flame. The safety device can be triggered by the partial or total
obstruction of the release conduit or the smoke channel.
The obstruction can be caused by internal or external influences, for
example:
- a release conduit with an inadequate configuration,
- the reduced diameter of the release conduit
- excessive direction changes (curves)
- counterslope.
The above circumstances obstructs the flow of flue gas to the out-
side. The safety device blocks the device, not allowing the flue gas
to fill the area where the device is installed. To again use the product
it is necessary to follow the instructions in the paragraph "OPERA-
TION"
If the device or its electrical connections breaks down, the machine
operation is blocked. If the machine is constantly blocked as a result
of the flue gas safety device, it is necessary to request the assistan-
ce of a qualified technician according to law in force, to check the
correct release of flue gas through the release conduit and/or the
smoke channel, according to the installation regulation.
It is highly prohibited to attempt to modify or remove the flue
gas safety device; this risks the safety of the user and persons
in the area.
Only a qualified technician who is authorised by the manufacturer
can meddle with the safety device in order to check it's functionality
or to substitute it if necessary.
If it is necessary to replace the device it is vital to only use "ori-
ginal parts" supplied by the manufacturer since it has been de-
signed, studied and regulated to be fitted with the water heater.
2.g Gas transformation
Transforming the product so it may receive a different type of gas
can be easily performed even while it is mounted. The instructions
for transforming and regulating the product to receive various types
of gas are below.
This operation must be performed by qualified personnel according
to law in force.
TRANSFORMATION FROM METHANE TO LPG
Transforming the product so it may receive a different type of gas
can be easily performed even while it is mounted.
Before any operation ensure that the gas supply is switched off.
I – SUBSTITUTION OF THE PILOT INJECTOR
- Disconnect the pilot flame tube (fig. 6)
- remove the pilot injector
- insert the injector and seal contained in the transformation kit (fig. 7),
II – SUBSTITUTION OF THE BURNER INJECTORS
- Remove the screws that hold the pilot flame in position (fig. 8)
- Remove the nut that holds the burner in place (fig. 9)
- Remove the screws that hold the diffuser in place (fig. 10)
- Unscrew the diffuser
- Unscrew the injectors and substitute them with those found in the
transformation kit
III – SUBSTITUTION OF THE MODULATION VALVE
- Loosen the cold water entry ramp nut on the exchanger
- Remove the 4 screws (B) of the gas valve (fig. 11)
- Separate the water/gas valve set
- Extract the large spring and the small spring/modulation valve set
(fig. 12)
- Substitute the modulation valve with the one in the kit
- Insert the valve and the large spring, taking care with the direction
of the insertion (fig. 14) and making sure that the drilled spring
guide disc is in its correct position (fig. 13)
- Remount the diffuser attaching it to the upper hole
IV – DISABLING THE PRESSURE REGULATOR
- Remove the protective lid
- Regulate the supply calibration screws so that the maximum
amount of gas can pass (disk completely horizontal)
After regulating seal the lid with paint, lacquer or other such
materials.
Note: It is necessary to use a pressure regulator that operates at 30
mbar for Butane Gas and at 37 mbar for Propane Gas. The
above values must be measured using a barometer connected
to the devices pressure entrance.