Default I/O connections

Default I/O connections of the ABB Standard macro are shown below.
1...10 kohm
max.
500 ohm
1)
All control boards do not have switches S1, S2 and S3. In that case, select voltage or
current for inputs AI1
Total load capacity of the Auxiliary voltage output +24V (X2:10) is 6.0 W (250 mA / 24 V DC).
Wire sizes:
2
0.2...2.5 mm
(24...14 AWG): Terminals +24V, DGND, DCOM, B+, A-, DGND, Ext. 24V
2
0.14...1.5 mm
(26...16 AWG): Terminals DI, AI, AO, AGND, RO, STO
Tightening torques: 0.5...0.6 N·m (0.4 lbf·ft)
S1
AI1 U/I
1)
S2
AI2 U/I
X1
Reference voltage and analog inputs and outputs
1
SCR
2
AI1
3
AGND
4
+10V
5
AI2
6
AGND
7
AO1
8
AO2
9
AGND
1)
S3
AO1 I/U
X2 & X3
Aux. voltage output and programmable digital inputs
10
+24V
11
DGND
12
DCOM
13
DI1
14
DI2
15
DI3
16
DI4
17
DI5
18
DI6
X6, X7, X8 Relay outputs
19
RO1C
20
RO1A
21
RO1B
22
RO2C
23
RO2A
24
RO2B
25
RO3C
26
RO3A
27
RO3B
X5
EIA-485 Modbus RTU
29
B+
30
A-
31
DGND
S4
TERM
S5
BIAS
X4
Safe torque off
34
OUT1
35
OUT2
36
SGND
37
IN1
38
IN2
AI2 and output AO1 with parameters. See the firmware manual.
and
EN – R0...R4 Quick installation guide 31
Voltage/Current selection for AI1:
Voltage/Current selection for AI2:
Signal cable shield (screen)
Output frequency/speed reference: 0...10 V
Analog input circuit common
Reference voltage 10 V DC
Not configured
Analog input circuit common
Output frequency: 0...20 mA
Output current: 0...20 mA
Analog output circuit common
Voltage/Current selection for AO1:
Aux. voltage output +24 V DC, max. 250 mA
Aux. voltage output common
Digital input common for all
Stop (0) / Start (1)
Forward (0) / Reverse (1)
Constant frequency/speed selection
Constant frequency/speed selection
Ramp set 1 (0) / Ramp set 2 (1)
Not configured
Ready run
250 V AC / 30 V DC
2 A
Running
250 V AC / 30 V DC
2 A
Fault (-1)
250 V AC / 30 V DC
2 A
Embedded Modbus RTU (EIA-485)
Serial data link termination switch
Serial data link bias resistors switch
Safe torque off. Factory connection. Both circuits
must be closed for the drive to start. See chapter
The Safe torque off function in ACS580-01 (0.75
to 250 kW) hardware manual (3AXD50000018826
[English]).
U
I
U
I
R0-
R4
R5
R6-
R9
I
U
EN
DA
DE
ES
FI
FR
IT
NL
PL
PT
RU
SV
TR
ZH
ZH

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Acs580-02Acs580-03Acs580-04Acs580-05

Tabla de contenido