9.5 Waiting step end
This function has been conceived to control kilns working cycles, whenever the
kiln cannot follow gradients programmed by the user. If at step end the diff erence
between process and setpoint values is greater than the value on
parameter 21 m.G.s.e. , controller starts with the next step only after waiting for the
time programmed on parameter 20 w.t.s.e. , or when this gap becomes lower than
parameter 21 m.G.s.e.
PROCESS
SETPOINT
Step 1
Step 2
Waiting time step end (Par. 20)
9.6 Loading default values
This procedure allows to restore all default settings.
Press stop and follow the points below:
Press
Press for 5". Green display shows 0000 with 1st digit fl ashing, red
1
CYCLE
display visualizes pass .
Flashing digit on green
2
display changes.
STEP
3
Device loads default settings.
STEP
Entering password 9999 all default parameters will be loaded. If it is necessary to
cancel and reset also the cycles, enter password 9989 .
18 - ATR902 - User manual
Step and max. gap (Par. 21)
Step 3
Display
To exit manually from this function press
. To disable this function fix at 0 end
step waiting time w.t.s.e. . During end step
waiting red display shows wait instead of
the cycle number.
Time
Enter the password 9999 .
Do