2.
Open the system filling tap located on the hydraulic unit and wait until
water begins to drain out of the valve.
3.
Switch on the electricity supply to the boiler, leaving the gas tap turned off.
4.
Activate a heat request via the room thermostat or the remote control
panel, so that the 3-way valve goes into heating mode.
5.
Activate a DHW request as follows:
heating only boilers connected to an external storage tank: activate
the thermostat on the storage tank;
6.
Carry on with the sequence until only water leaks out of the manual
air vent valve, and the air flow has stopped. Close the manual air vent
valve.
7.
Check the system pressure level is correct (the ideal level is 1 bar).
8.
Turn off the system filling tap.
9.
Turn on the gas tap and ignite the boiler.
3.11 Flue gas discharge and air suction
Observe local legislation regarding flue gas discharge.
Flue gases are discharged from a centrifugal fan located inside the combus-
tion chamber and the control board constantly checks that this is working
correctly. The boiler is supplied without the flue gas discharge/air suction kit,
since it is possible to use the accessories for appliance with a forced draught
sealed chamber that better adapts to the installation characteristics.
For flue gas extraction and the restoration of boiler combustion air, it is essen-
tial to only use certified piping. Connection must be carried out correctly as in-
dicated in the instructions supplied as standard with the flue gas accessories.
Multiple appliances can be connected to a single smoke pipe provided that
each is a sealed chamber-type appliance. The boiler is a Type C appliance
(sealed chamber), and must therefore have a safe connection to the flue
gas discharge pipe and to the combustion air suction pipe; these both carry
their contents outside, and are essential for the operation of the appliance.
The maximum lengths of the ducts refer to flue systems available in
the catalogue.
POSSIBLE OUTLET CONFIGURATIONS (fig. 23)
B23P/B53P Suction indoors and discharge outdoors
C13-C13x Discharge via concentric wall outlet. The pipes may leave the
boiler independently, but the outlets must be concentric or sufficiently close
together to be subjected to similar wind conditions (within 50 cm)
C33-C33x Discharge via concentric roof outlet. Outlets as for C13
C43-C43x Discharge and suction in common separate smoke pipes, but
subjected to similar wind conditions
C53-C53x Separate discharge and suction lines on wall or roof and in areas
with different pressures. The discharge and suction lines must never be
positioned on opposite walls
C63-C63x Discharge and suction lines using pipes marketed and certified
separately (1856/1)
C83-C83x Discharge via single or common smoke pipe and wall suction line
C93-C93x Discharge on roof (similar to C33) and air suction from a single
existing smoke pipe
"FORCED OPEN" INSTALLATION (TYPE B23P/B53P)
Flue gas discharge pipe ø 80 mm (fig. 20)
The flue gas discharge pipe can be directed to the most suitable direction
according to installation requirements. For installation, follow the instruc-
tions supplied with the kit. In this configuration, the boiler is connected to
the flue gas discharge pipe (ø 80 mm) through an adaptor (ø 60-80 mm).
The B23P/B53P configuration is forbitten in case of installation in
pressurised collective chimney (3CEp).
In this case, the combustion air is picked up from the boiler instal-
lation room (which must be a suitable technical room with proper
ventilation).
Uninsulated flue discharge outlet pipes are potential sources of danger.
Arrange the flue gas discharge pipe so it slopes by 3° towards the boiler.
The boiler automatically adapts the purging to the type of installation
and the length of the pipe.
maximum length* of the flue gas
discharge pipe ø 80 mm
70 m
*"Straight length" means without bends, drainage terminals or joints.
"SEALED" INSTALLATION (TYPE C)
The boiler must be connected to concentric or twin flue gas discharge pipes
and air suction pipes, both leading outdoors. The boiler must not be oper-
ated without them.
Concentric pipes (ø 60-100 mm) (fig.21)
The concentric pipes can be placed in the most suitable direction according
to installation requirements, complying with the maximum lengths indicated
in the table.
Arrange the flue gas discharge pipe so it slopes by 3° towards the
boiler.
pressure drop
45° bend
90° bend
1 m
1,5 m
Non-insulated outlet pipes are potential sources of danger.
The boiler automatically adapts the purging to the type of installation
and the length of the pipe.
Do not obstruct or choke the combustion air suction pipe in any way.
For installation, follow the instructions supplied with the kit.
Horizontal
straight length *
concentric pipe ø 60-100 mm
5,85 m
*"Straight length" means without bends, drainage terminals or joints.
Vertical
straight length *
concentric pipe ø 60-100 mm
6,85 m
*"Straight length" means without bends, drainage terminals or joints.
Concentric pipes (ø 80-125)
For this configuration, the special adaptor kit must be fitted. The concentric
pipes can face in the direction most suitable for installation requirements.
For installation, follow the instructions supplied with the specific condensing
boilers kits.
straight length *
concentric pipe ø 80-125 mm
15,3 m
*"Straight length" means without bends, drainage terminals or joints.
Twin pipes (ø 80 mm) (fig. 22)
The twin pipes can face in the direction most suited to the installation re-
quirements. For installation, follow the instructions supplied with the spe-
cific accessory kit for condensing boilers.
To use the combustion air suction pipe, one of the two inlets (A and B) must
be selected. Remove the closure plug which is fixed using screws, and use
the specific adaptor relating to the inlet selected (C air inlet adaptor ø 80 - D
air inlet adaptor from ø 60 to ø 80) available as an accessory.
Arrange the flue gas discharge pipe so it slopes by 3° towards the
boiler.
The boiler automatically adapts the purging to the type of installation and
the length of the pipes. Do not obstruct or choke the pipes in any way.
Refer to the graphs to find the maximum lengths of the single pipe.
The use of longer pipes reduces the boiler output.
maximum straight length *
twin pipes ø 80 mm
45+45 m
*"Straight length" means without bends, drainage terminals or joints.
PRESSURISED COLLECTIVE CHIMNEY 3CEp
3CEp installations are available only with the dedicated accessory
(optional).
The B23P/B53P configuration is forbitten in case of installation in
pressurised collective chimney.
Maximum pressure of the pressurised collective chimney must not
exceed the 35 Pascal.
Maintenance in case of pressurised collective chimney must be
performed as indicated in the specific chapter "Maintenance in-
structions".
For 3CEp installations with dedicated accessory, it is necessary
change the setting of minimum fan speed according the accessory
instructions.
ENGLISH
pressure drop
45° bend
90° bend
1,3 m
1,6 m
pressure drop
45° bend
90° bend
1,3 m
1,6 m
pressure drop
45° bend
90° bend
1,0 m
1,5 m
pressure drop
45° bend
90° bend
1,0 m
1,5 m
7