Note On Adding Refrigerant - EAS ELECTRIC R32 Manual De Usuario

Ocultar thumbs Ver también para R32:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

Note on Adding Refrigerant

Some systems require additional charging depending on pipe lengths. The standard pipe length varies
according to local regulations. For example, in North America, the standard pipe length is 7.5m (25').
In other areas, the standard pipe length is 5m (16'). The refrigerant should be charged from the service
port on the outdoor unit' s low pressure valve. The additional refrigerant to be charged can be
calculated using the following formula:
R32 :
CAUTION
DO NOT
φ6.35(1/4")
(Total pipe length -
standard pipe length)x
12g(0.13oZ)/m(ft)
mix refrigerant types.
Liquid Side Diameter
φ9.52(3/8")
φ12.7(1/2")
(Total pipe length -
(Total pipe length -
standard pipe length)x
standard pipe length)x
24g(0.26oZ)/m(ft)
40g(0.42oZ)/m(ft)
Page 37
V.2

Hide quick links:

Publicidad

Capítulos

Tabla de contenido
loading

Este manual también es adecuado para:

R290

Tabla de contenido