PR 9113 Manual De Instalación página 50

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

Safety Manual
Name
OuT.eRR
OuT.LO
OuT.HI
ReSp
uSe.CaL
12
9113 TeMpeRaTuRe / ma CONVeRTeR
Function
Fixed output value on detected sensor error:
NONe = Sensor error detection NOT enabled, output at sensor
error is undefined.
The end user must ensure that the applied sensor including
wiring has a failure rate qualifying it for the safety application
without the detection enabled.
0 ma = Output is 0 ma at sensor error
3.5 ma = Output is 3.5 ma at sensor error (Ne43 downscale)
23 ma = Output is 23 ma at sensor error (Ne4 upscale)
Selected temperature value for 0% output for CH1.TYp = TeMp
in units defined by the uNIT parameter (°C or °F)
Range is defined by the selected temperature sensor (SeNSOR
and TC.TYpe, Ni.TYpe or pt.TYpe), but value must be less than
OuT.HI - minimum span.
Selected temperature value for 100% output for CH1.TYp =
TeMp in units defined by the uNIT parameter (°C or °F).
Range is defined by the selected temperature sensor (SeNSOR
and TC.TYpe, Ni.TYpe or pt.TYpe), but must be larger than
OuT.LO + minimum span.
analogue output response time in seconds.
Range is 0.0 to 60.0 seconds.
use the applied process calibration values:
NO = The last performed process calibration on Channel1 is not
used. The channel operates with accuracy as specified.
YeS = The last performed process calibration on Channel1 is
in operation. The required accuracy must be verified by user.
end user must verify by test that the applied process calibration
does not introduce failures exceeding the requirements for the
safety application.
Version No. V5R0

Publicidad

Capítulos

Tabla de contenido
loading

Productos relacionados para PR 9113

Este manual también es adecuado para:

9113a9113b

Tabla de contenido