Check that ignition occurs regularly, because when the
!
device has been moved forwards, it could occur that
the air velocity in exit is so high as to render ignition
difficult. If this happens, move it backwards, gradually,
until it reaches the correct position and ignition occurs
regularly. This position should be definitive.
It should be kept in mind that it is preferable, for the first fla-
me, to limit the amount of air to that strictly necessary in order
to ensure safe ignition even in difficult circumstances.

GENERAL DIAGRAM AIR REGULATION

INCORRECT REGULATION
Combustion air inlet with very locked shutter
CORRECT REGULATION
Combustion air inlet with very opened shutter
Combustion head
Air flow large
opening
Control and fixing knobs of combustion head
Combustion head
Air flow
quite locked.
Attention:
Avoid complete
locking
Control and fixing knobs of combustion head