INSTRUCTIONS FOR SETTING SIEMENS SKP 15.000 E2 GAS VALVE
DESCRIPTION OF HOW THE VALVE OPERATES
Single-stage valves
When the valve receives the signal to open, the pump cuts in and
the magnetic valve closes. The pump transfers the oil from under the
piston to above it, forcing the piston downward, which compresses
the closure return spring with the rod and plate. The valve remains
in the open position while the pump and magnetic valve remain
powered.
When the unit receives the signal to close (or if power supply is cut
off) the pump shuts down, the magnetic valve opens decompressing
the chamber above the piston. The plate is closed both by the return
spring and by gas pressure. The flow rate for this valve is calculated
to ensure full closure in less than 0.6 seconds.
This type of valve cannot regulate the gas flow rate (closure/
opening).
INSTRUCTIONS FOR HONEYWELL GAS VALVES UNIVERSAL GAS VALVES TYPE: VE 4000A1
(....A .... = Opening - Closure, rapid)
The VE 4000A1 valves are Class A solenoid valves,
normally closed. They may be used as ON/OFF
valves in the supply trains with Natural Gas, Ma-
nufactured Gas or GPL, on burners or combustion
installations.
They are provided with M.I. and CE Approval for
EN161.
FEATURES
- Valves normally closed
- Without flow regulator
- Rapid opening and closing
SKP 15...
complete with valve
23 / 30
0006080115_200909
E
N
G
L
I
S
H