BONFIGLIOLI Vectron ACTIVE CUBE Serie Guia De Inicio Rapido página 64

Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

Enter the motor data indicated on the rating plate in the following parameters.
Use the arrow keys to select the required parameter and edit the parameter value.
Use the ENT key to confirm the selected parameter and the parameter values entered.
GB
Note the warnings and error messages displayed during guided commissioning.
To ignore the warning messages, press the ENT key. The guided commissioning is continued. However, it is
recommended that the data be checked and corrected if necessary.
To correct the entered parameter values after the warning or error message, press the ESC key. Use the arrow
keys to switch to the parameter value to be corrected.
Note the warnings or error messages upon completion of the parameter identification.
For release of the output stage, wiring of digital inputs S1IND (STOA) and S7IND (STOB) is
required.
In the case of higher requirements as regards the accuracy of the speed/torque control, you
should carry out the guided commissioning procedure once again under operating conditions
because part of the machine data depends on the operating temperature.
During this procedure, confirm the rated machine values already entered.
64
No.
Description
Rated Voltage
370
Rated Current
371
Rated Speed
372
The rated data of the motor are to be entered according to the specifications on the rating plate
for the motor connection Type used (star or delta connection). If the data entered deviate from
the rating plate, the parameters will not be identified correctly. The rated data is to be
parameterized as per the motor rating plate. Consider the increased rated current of the
connected three-phase motor when the motor is switched from star to delta.
After input of the machine data, the calculation or examination of the parameters is started
automatically. The display changes over to "CALC" for a short time. If the verification of the
entered machine data is successful, the guided commissioning procedure continues with the
identification of the parameters (automatic measurement of further machine data).
Further machine data are measured while the drive is at a standstill. These measurements will
be entered automatically in the relevant parameters by the parameter identification feature.
Confirm the display "PAidE" by pressing the ENT key.
No signals at digital inputs S1IND (STOA) and S7IND (STOB). If signals were already applied at
the beginning of the guided commissioning, the "StO" message is not displayed.
Confirm the final "rEAdY" message by pressing the ENT key.
Canceling the operation with the ESC key or withdrawing the enable signal S1IND
(STOA) or S7IND (STOP) results in an incomplete take-over of the values.
Confirm the "End" display by pressing the ENT key.
The guided commissioning of the frequency inverter is terminated via a reset and the
initialization of the frequency inverter. The relay output X10 signals a fault.
After successful initialization of the frequency inverter, the factory-set parameter
241 is displayed.
frequency
The drive is accelerated to the set
signals at digital inputs S1IND (STOA) and S7IND (STOB) and
Start clockwise by rising signal edge at S2IND or

 S tart anticlockwise by rising signal edge at S3IND
No.
374
Rated Cosine Phi
375
Rated Frequency
376
Rated Mechanical Power
418 (default 3.50 Hz) by:
Min. frequency
Quick Start Guide ACU
Description
Actual
02/15

Hide quick links:

Publicidad

Tabla de contenido
loading

Tabla de contenido