Status Messages During Commissioning (Ss; Warning And Error Messages During Commissioning (Sa - BONFIGLIOLI Vectron ACTIVE CUBE Serie Guia De Inicio Rapido

Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

7.2

Status messages during commissioning (SS...)

The following status messages are possible when Setup is run:
Status message
SS000
OK
SS001
PC Phase 1
PC Phase 2
SS002
SS003
STO
SS004
Parameter
Identification
Setup already active
SS010
SS030
No release signal
Error – see 259
SS031
SS032
Warning Phase
Asymmetry
SS099
Setup not carried
out yet.
7.3
Warning and error messages during commissioning (SA.../SF...)
Code
SA000
No warning message present.
SA001
The value of the parameter
inverter The maximum reference voltage is indicated on the nameplate of the frequency inverter.
SA002
For a three-phase motor, the calculated efficiency is in the limit range. Check the values entered for
parameters
Rated Voltage
SA003
The value entered for parameter
Check the value.
SA004
For three-phase motor, the calculated slip is in the limit range. Check the values entered for
parameters
Rated Speed
Code
SA011
Current Controller non typical value; refer to the Operating Instructions.
SA012
Current Controller non typical value with 2 kHz; refer to the Operating Instructions.
SA014
Current Controller non typical value with 4 kHz; refer to the Operating Instructions.
SA018
Current Controller non typical value with 8 kHz; refer to the Operating Instructions.
SA0021
Stator resistance (SA0021) or rotor resistance (SA0022) is very high. The following causes are possible:
SA0022
The motor cable cross-section is not sufficient.
The motor cables are too long.
The motor cables are not connected correctly.
The contacts are not in a proper condition (corrosion).
SA031
Shorten Motor Line using Switching frequency 16 kHz.
SA032
Shorten Motor Line using Switching frequency 12 kHz and higher.
SA033
Shorten Motor Line using Switching frequency 8 kHz and higher.
The slip speed was not determined correctly. Check the values entered for parameter
SA041
372 and
Rated Speed
The slip speed was not determined correctly. Check the values entered for parameter
SA042
372 and
Rated Speed
02/15
Auto set-up routine has been carried out.
The plausibility check (PC) of the motor data is active.
The calculation of dependent parameters is active.
The parameter identification requires release on digital input STOA and
STOB.
The rated motor values are checked by the parameter identification feature.
The setup routine via the control panel is being carried out.
The parameter identification requires controller release on digital inputs STOA
and STOB.
Error during the auto set-up routine. Check the value of
The parameter identification feature diagnosed an unbalance during the
measurements in the three motor phases.
Self-setup has not yet been carried out.
Warning messages during guided commissioning
Meaning / Measure
370 is out of the rated voltage range of the frequency
Rated Voltage
370,
Rated Current
Rated Cos phi
372 and
Rated Frequency
Warning messages after guided commissioning
Meaning / Measure
375.
Rated Frequency
375.
Rated Frequency
Quick Start Guide ACU
Meaning
371 and
376.
Rated Power
374 is outside of the normal range (0.6 to 0.95).
375.
259.
Current Error
71
GB

Hide quick links:

Publicidad

Tabla de contenido
loading

Tabla de contenido