7 Control unit messages

LED
green
red
Display
off
off
-
on
on
-
flashing
off
RUN flashing
on
off
RUN
on
flashing
RUN + WARN
flashing
flashing
RUN + WARN
off
flashing
FAULT flashing
off
on
FAULT
7.1

Warning and error messages during operation

The code displayed via parameter
A0088 signals warnings A0008 + A0080, for example.
Key
A0000
No warning present.
A0001
Frequency inverter overloaded, warning code (A0002 or A0004)
A0002
Frequency inverter overload (60 s). Check load behavior.
A0004
Short-term overload (1 s). Check motor and application parameters.
A0008
Max. heat sink temperature reached, check cooling system and fan.
A0010
Max. interior temperature reached, check cooling system and fan.
A0020
Speed set point is limited by a controller.
A0080
Max. motor temperature reached, check motor and sensor.
A0100
Mains phase failure, check mains fuses and supply cable.
A0400
Limit frequency reached; output frequency is limited.
A4000
DC link voltage has reached the Type-specific minimum.
Current Error 259 and
shown error code.
The error message can be acknowledged via the control unit buttons and digital input STO.
Key
00
No fault has occurred.
F00
Frequency inverter overloaded (60 s), check load behavior
F01
02
03
Short-term overload (1 s), check motor and application parameters
F02
00
Heat sink temperature too high, check cooling system and fan.
Temperature sensor defective or ambient temperature too low.
01
02/15

Status indication

Description
no supply voltage
initialization and self-test
ready, no output signal
operating message
Operational message, current
Ready for operation, current
259 of frequency inverter
Current Error
259, acknowledge fault
Current Error
269 can be composed of several messages. Key
Warnings
Warning messages
Meaning
310 facilitates troubleshooting and error diagnosis with the
Last Error
Error messages
Meaning
Overload
Heat sink
Quick Start Guide ACU
Rotary field on motor
no
no
no
yes
269
yes
Warning
269
no
Warning
no
no
GB
69

Hide quick links: