Connections and indicators (see also the section "Terminal Diagram")
Terminal
Function
A1
Operating voltage connection U
A2
Operating voltage connection Ground
X1/X2
Semiconductor signal outputs for indicating and
evaluating operating and error statuses
S1
Input for function selection (operating mode)
S2
Input for function selection (operating mode)
I1 - I4
Input for function selection (operating mode)
I2 - I4
I5
Input for RESET function
I6
Input for enable/start delay
Q1/Q2
Outputs (semiconductors), safety related
Q3/Q4
Inverted outputs (semiconductors), safety related
Settings of the standstill monitor (diagram)
MSI-SR-SM42OS-xx
Information on the outputs
The outputs Q1/Q2 can be used up to SIL 3.
The outputs Q3/Q4 can be used for controlling magnetically
operated interlocks up to SIL 1.
Setting of the speed to be monitored
The standstill frequency is set using the two rotary switches "x"
and "y".
Rotary switch
00 / 01 - 99
"ENTER" button: Activation of the function block and control circuit
functions
• Set the required operating mode, speed (at the rotary switches)
and the control circuit function (using external wiring at S1, S2,
I5).
• Then apply the operating voltage with the ENTER button
pressed; the ERR indicator flashes (max. 3 s).
• Release the ENTER button while the ERR indicator is flashing
(an error is detected if the ENTER button is pressed for longer
than 3 s).
The selected operating mode, speed and RESET function are
then saved and active.
Leuze electronic GmbH + Co. KG
info@leuze.de
• www.leuze.com
B
Freq. [Hz]
0,5 / 01 - 99
In der Braike 1 D-73277 Owen
Tel. +49 (0) 7021 573-0
LED
Meaning, if LED lights
PWR
U
is present
B
S1
High signal is present
S2
High signal is present
I1 - I4
High signal is present
I5
High signal is present
I6
High signal is present
Q1/Q2
High signal is present
Q3/Q4
High signal is present
ERR
Error
X1/X2
are not safe semiconductor outputs.
X1
signals error states.
X2
signals the logic state of A and the RESET
request by I5.
RESET/BYPASS function I5/I6
The automatic (high)/manual (low) Reset function is defined
during the activation of the POU (see ENTER button).
• automatic RESET: A High signal at I5 (open) transmits the
comparator signal to the outputs.
• manual RESET: A High pulse at I5 transmits the enable of the
comparator to the outputs.
The transfer of the Reset signals can be influenced using
the Bypass function (ODER) at the input I6 of the
MSI-SR-SM42OS, If the input I6 is wired (HIGH), the outputs
Q1 and Q2 are permanently HIGH and Q3 and Q4 permanently
LOW. The generation of the bypass signal has to fulfill the same
safety requirements as the operating mode and the designated
safety function.