Technical Data; Specifications - SMA MLX Serie Guia De Instalacion

Ocultar thumbs Ver también para MLX Serie:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

Technical Data

5 Technical Data

5.1 Specifications

Parameter
AC
1)
Rated apparent power
2)
Rated active power
1)
Reactive power range
Rated grid voltage (voltage range)
Grounding schemes supported
Rated current AC
Max. current AC
AC current distortion (THD at nominal output power)
Power factor default
Power factor - regulated
Stand-by power consumption (comm. only)
Rated grid frequency (frequency range)
DC
Input voltage range
Rated voltage DC
MPPT voltage range - rated power
Max. voltage DC
Min. on grid power
Max. MPPT current DC
Max. short-circuit current DC
MPP tracker / Input per MPPT
Efficiency
Max. efficiency
EU / CEC efficiency at V
dc,r
MPPT efficiency static
Enclosure
Dimensions (H x W x D)
Weight
Acoustic noise level
Table 5.1 Specifications
1)
At rated grid voltage.
2)
At rated grid voltage, Cos(phi)=1.
3P + PE (delta or WYE) / 400-480 V (+/- 10%)
3)
Depending on installed options.
L00410644-01_2q / Rev. date: 2014-06-02
MLX 60
60 kVA
60 kW
0–36 kVAr
TT, TN
3 x 87 A
3 x 87 A
< 5%
> 0.99 at rated power
0.8 over-excited, 0.8 under-excited
3 W
50/60 Hz (+/- 10%)
565–1000 V @ 400 V
ac
680–1000 V @ 480 V
ac
630 V @ 400 V
ac
710 V @ 480 V
ac
570–800 V @ 400 V
ac
685–800 V @ 480 V
ac
1000 V
100 W
110 A
150 A
1 / 1 (external string combining)
98.6% (preliminary value)
98.0% / 98.0% (preliminary value)
99.9% (preliminary value)
740 × 570 × 300 mm (29 × 22.5 × 12 in)
3)
75 kg (165 lbs)
55 dB(A) (preliminary value)
5
5
31

Publicidad

Tabla de contenido

Solución de problemas

loading

Este manual también es adecuado para:

Mlx 60 ul

Tabla de contenido