Technical Data
Parameter
Electrical
Electrical Safety
PELV on the communication and control card
Functional
Functional Safety
5
5
Islanding detection - loss of mains
RCD compatibility
Table 5.2 Safety Specifications
1)
Depending on local regulations.
5.2 Trip Settings
Illustration 5.1 Over-voltage and Under-voltage Disconnect
Nom. grid
Nom. voltage 400 V
Nom. voltage 480 V
Table 5.3 Default Voltage Trip Levels and Trip Times
32
1)
U
2
T_U
min
min
[V]
[s]
Default
200.00
0.16
Range
160-240
0.1-3.0
Default
240.00
0.16
Range
192-288
0.1-3.0
L00410644-01_2q / Rev. date: 2014-06-02
MLX series
•
IEC 62109-1/IEC 62109-2 (Class I, grounded – communication part
Class II, PELV)
•
UL 1741 with non-Isolated EPS Interactive PV Inverters
•
IEEE 1547
Class II
•
Voltage and frequency surveillance
•
DC content of AC current surveillance
•
Insulation resistance surveillance
•
Residual current monitoring
•
UL1998
•
Active frequency shift
•
Disconnection
•
3-phase monitoring
•
ROCOF/SFS
Type B, 600 mA
2
U
1
T_U
1
U
min
min
max
[V]
[s]
[V]
352.00
2.00
440.00
300-380
0.5-3.0
420-480
423.00
2.00
528.00
360-456
0.5-3.0
504-576
1
T_U
1
U
2
max
max
[s]
[V]
1.00
480.00
0.5-3.0
440-520
1.00
576.00
0.5-3.0
528-624
T_U
2
max
[s]
0.16
0.1-3.0
0.16
0.1-3.0