Cycle time extension (Vario)
11 Cycle time extension (Vario)
Designation
Cycle time extension
11.1 Exploded view
Fig. 23
1
BCD switch
11.2 Function
The cycle time extension extends the cycle time of the electrical actuator. For this, the
actuator moves to the end positions in a clocked manner (OPEN or CLOSED) or to the
middle position (if accessory for middle positioning is present).
Switch position for 90° cycle, see Table. Cycle time without mounted switches = 5 s for
90 ° on EA21; 15 s for 90 ° on EA31; 25 s for 90 ° on EA42.
Switch position
0 Delivery position
1
2
3
4
5
6
7
Switch positions 8 – 9 have the function of switch position 7. The cycle time extension
is also active in case of a malfunction or in combination with the reset unit accessory.
I.e. in case of a power failure, the end positions are approached with a delay.
82
Technical data
2
EA 21
8
12
15
19
25
30
35
35
Accessories for electrical actuators
Code
199 190 080
1
2
LED
75 Cycle time (s)
EA 31
EA 42
20
30
25
35
30
40
35
45
40
50
50
55
60
65
60
75