Overview On Activation; Setting The End Positions - Georg Fischer EA11 Manual Instrucciones

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

Accessories for electrical actuators
 Connect the connector for the middle position to terminal 3.

15.4 Overview on activation

Actuator moves in
position
Open
CLOSED
Middle
* CCW - counterclockwise
** CW – clockwise, rotational direction seen from above on the indicator
 Move actuator to position "OPEN" (CCW). For this, energize terminal 1.
Limit switch S1 is activated.
 Move actuator to position "CLOSED" (CW). For this, energize terminal 2.
Limit switch S2 is activated.
 Move actuator to middle position (CCW/CW). For this, energize terminal 3.
Switches S3/S4 are activated.

15.5 Setting the end positions

In order to set the opening angle from 90° to 180°:
 Turn switching cam 2 of limit switch S2 by 90 ° anti-clockwise (seen from above).
 Reconnect the device to the supply voltage.
 Move the actuator into position "CLOSED" (terminal 2 energized).
 Readjust cam 2 until the desired end position is reached (see position of the ball).
 Replace the standard position indicator with the new 3-way position indicator.
Standard position indicator
Terminal energized
1
2
3
3
Activated switch(es)
S1
S2
S3
S4
e.g.
3-way position indicator
Middle position
Rotational direction
of the actuator
CCW*
CW**
CCW*
CW**
Ball with
T-port
89

Publicidad