LAURA 20/20F & VICTORIA 20/20F
HORIZONTAL COAXIAL FLUE TERMINAL LOCATION
= VENT TERMINAL
Fig. 16
A = 12"
clearances above grade, veranda, porch, deck or balcony
B = 12"
clearances to window or door that may be opened
D = 18"
vertical clearance to ventilated soffi t located above the terminal within a horizontal distance of 2 feet (60 cm) from the
centre line of the terminal
E = 18"
clearance to unventilated soffi t
F = 9"
clearance to outside corner
G = 6"
clearance to inside corner
H = 4 ft. (U.S.A.)
not to be installed above a gas meter/regulator assembly within H horizontally from the centre line of the regulator
I =
3 ft. (U.S.A.)
clearance to service regulator vent outlet
6 ft. (Canada)
J =
9" (U.S.A.)
clearance to non-mechanical air supply inlet to building or the combustion air inlet to any other appliance
K = 3 ft. (U.S.A.)
clearance to a mechanical air supply inlet
6 ft. (Canada)
* L = 7 ft.
clearance above paved side-walk or a paved driveway located on public property
** M = 18"
clearance under veranda, porch, deck or balcony
*
a vent shall not terminate directly above a side-walk or paved driveway
which is located between two single family dwellings and serves both
dwellings unless terminated 7ft above sidewalk.
** only permitted if veranda, porch, deck or balcony is fully open on a
minimum of 2 sides beneath the fl oor.
Note: local Codes or Regulations may require different clearances.
The fl ue terminal must be exposed to the external air and the position
must allow the free passage of air across it at all times. In certain weather
conditions the terminal may emit a plume of steam. Avoid positioning the
terminal where this may cause a nuisance.
If the terminal is fi tted less than 6.56 ft / 2 m above a surface to which
people have access, the terminal must be protected by a terminal guard.
= AIR SUPPLY INLET
Vent Termination Minimum Clearances
ouvrable
fixé fermé
14
= AREA WHERE TERMINAL IS NOT PERMITTED