LEROY-SOMER
4.9 - Configuration 6: Jog operation command
power supply
Remote control
power supply
Marking
Functions - Characteristics
Connection of protected mains supply phases
L1, L2 or 200V to 240V ± 10% 50-60Hz in single-phase
L1, L2, L3 220V to 480V ± 10%, 50-60Hz in three-phase
PE
Earth connection
Connection of the braking resistor (optional)
R1, R2
VMA21 - min. resistance value = 200 Ohms
VMA22 - min. resistance value = 200 Ohms
Locking logic input
1
Terminals 1 and 3 not connected: drive disabled
Terminals 1 and 3 connected: drive enabled
Speed analogue output 0 to +10V, 3mA or analogue
input 0-10V - 4-20mA
2
0V = zero speed
10V = maximum speed
Source +24VDC, 30mA
3
Common at terminal 10
4
Source +10V, 10mA
5
0 V
Reference input 0 to +10V or 4-20mA
6
0-10V: input impedance = 100kOhms
4-20mA: input impedance = 0.5kOhms
7
Run Reverse logic input
8
Run Forward logic input
9
Stop and run authorisation logic input
Source +24VDC, 30mA
10
Common at terminal 3
Fault relay - volt-free contact 250V 1A
11, 12
Contact open: switched off or faulty
Contact closed: running
78
PARAMETER SETTING MANUAL
VARMECA 20
Variable speed motors and geared motors
WIRING DIAGRAMS
Mains
KM1
QS
AU
Braking
resistor
SB1
(Optional)
SB2
KM1
KM1
QS : Fused isolator
AU : Emergency stop
SB1 : Off button
SB2 : On button
VARMECA 20
1
L1
2
L2
3
+24V
L3
4
+10V
5
0V
PE
6
7
SA3
R1
8
SA4
R2
9
SA5
10
+24V
11
Fault relay
12
Associated parameter setting
CDC-VMA 20
P14 = Config. 6
Reference
0 -10V
4 -20mA
3532 - 05.2004 / f
Control
potentiometer
Reverse
Forward
Stop
PEGASE VMA 20
Terminal block configuration = Config. 6
Mini Dip K1
ON
OFF