10.1.- FILTER MEDIA

The filter media included in the air inlet filters of the AFQm IP54 cabinet require cleaning. The outlet
filters do not require maintenance.
Inlet filters
Figure 72: AFQm IP54 inlet filters.
The cleaning frequency will depend on the environmental conditions where the device is installed, as
well as on how the device is used.
The filter media can be removed from outside the door. The device does not have to be opened or taken
offline. To do this, open the filter cover by pressing the tab (
).
Figure 73
Figure 73: Removal of filter media.
The device uses G3 filter media. The pads have to be replaced, or shaken out or air cleaned to remove
the dirt.
If the excess dirt in the filter media significantly affects the operation of the device, the AFQm IP54 will
display an alarm per screen. This will happen when the air flow is so reduced that the device cannot
exceed 50% of its operating capacity.
In any case, the filter media should be cleaned at least once a year.