Descargar Imprimir esta página

WEG CFW700 Serie Referencia Rápida De Los Parámetros, Fallas Y Alarmas página 23

Ocultar thumbs Ver también para CFW700 Serie:

Publicidad

Idiomas disponibles

Idiomas disponibles

Quick Parameter Reference, Faults and Alarms
Fault/Alarm
F006:
The mains voltage imbalance is too
Input Voltage
high or phase loss at the supply line has
Imbalance or
occurred.
Phase Loss
Note:
- This fault may not occur if the load at
the motor shaft is too low or nonexistent.
P0357 sets the time for the trip, and
P0357 = 0 disables this fault.
F021:
A DC link undervoltage condition has
DC Link
occurred.
Undervoltage
F022:
A DC link overvoltage condition has
DC Link
occurred.
Overvoltage
A046:
It is the motor overload alarm.
High Load at the
Note:
Motor
It can be disabled by setting P0348 =
0 or 2.
A047:
It is the IGBT overload alarm.
IGBT Overload
Note:
Alarm
It can be disabled by setting P0350 =
0 or 2.
F048:
It is the IGBT overload fault.
IGBT Overload
Fault
A050:
The NTC temperature sensors located in
IGBT High
the IGBTs detected a high temperature
Temperature
alarm.
Note:
It can be disabled by setting P0353 =
2 or 3.
F051:
The NTC temperature sensors located in
IGBT
the IGBTs detected a high temperature
Overtemperature
fault.
F067:
Fault related to the phase relationship
between the encoder signals, if P0202 =
Inverted
5 and P0408 = 2, 3 or 4.
Encoder/
Note:
Motor Wiring
- This fault can only occur during the self-
tuning routine.
- It is not possible to reset this fault.
- In case of fault, turn off the power
supply, solve the problem, and then turn
it on again.
22 | CFW700
Description
Possible Causes
A Phase Loss at the inverter input.
The input voltage imbalance is > 5 %.
The input voltage is too low and the DC link voltage
dropped below the minimum permitted value (monitor
the P0004 parameter value):
Ud < 223 V - 200-240 V three-phase input voltage;
Ud < 170 V - 200-240 V single-phase input voltage
(CFW700XXXXS2 or CFW700XXXXB2 models)
(P0296 = 0);
Ud < 385 V - 380 V input voltage (P0296 = 1);
Ud < 405 V - 400-415 V input voltage (P0296 = 2);
Ud < 446 V - 440-460 V input voltage (P0296 = 3);
Ud < 487 V - 480 V input voltage (P0296 = 4).
Phase loss at the inverter input.
Pre-charge circuit failure.
Parameter P0296 was set to a value higher than the
power supply rated voltage.
Too high input voltage, resulting in a DC link voltage
higher than the maximum permitted value:
Ud > 400 V - 220-230 V models (P0296 = 0);
Ud > 800 V - 380-480 V models (P0296 = 1, 2, 3,
or 4).
The inertia of the driven-load is too high or the
deceleration time is too short.
The parameter P0151, P0153 or P0185 setting is
too high.
The settings of P0156, P0157 and P0158 are too low
for the used motor.
There is excessive load at the motor shaft.
The inverter output current is too high.
The inverter output current is too high.
High surrounding air temperature (>50 °C (122 °F)) and
high output current.
Blocked or defective fan.
Very dirty heatsink.
Output motor cables U, V, W are inverted.
Encoder channels A and B are inverted.
Error in the encoder mounting position.

Publicidad

loading