Technical specifications

Test voltages
Scope
Short circuit current
Test voltages accuracy
Megohmmeter basic accu-
racy
Advanced features
Built-in printer
Serial data output
MegaLogg2 Software
Memory up to 4000 readings
Built-in chronometer
:
500, 1000, 2500, 5000 V with fast selection.
500 V to 5 kV in 100 V or 500 V steps. DC, negative in
relation to grounding.
:
5TΩ @ 5 kV
:
1,5 ± 0,5mA
:
± 3% of nominal value over a 10 GΩ resistance
:
5% of reading ± 3 digits ±
(1 MΩ to 500 GΩ at any test voltage)
:
Automated Polarization Index computing
Automated Dielectric Absorption Ratio computing
Step Voltage Test
Programmable timer with 30 seconds, 1min, 10min and
30 min duration.
"Pass-fail test" with programmable limits.
:
Prints elapsed time, actual voltage applied to the charge
and measured resistance.
:
RS-232 @ 4800 bps. It allows the connection to a serial
printer, to a portable computer or a laptop, or to a data-
logger.
:
It allows for the downloading of the data stored in memory
and for the synchronization of the megohmeter internal
clock with the date and real time.
:
It allows for the storage of 4000 tests readings in its internal
NVRAM memory. Those readings can be downloaded to a
computer with Windows™ 9x – Me – NT4.0 – 2000 or XP
operative system, by means of the MegaLogg2 software.
:
Shows elapsed time since measurement stats in mm:ss
format.