Electrical connections
Analog / HART module
11
Shield
12
+ I out analog output / HART
13
- I out analog output / HART
14
+ 24 V DC for external supply, 30 mA max.
15
GND 24 V
16
D out 1
17
D out 2
18
GND D out (D out 1 + 2)
19
D in 1
20
D in 2
21
GND D in (D in 1 + 2)
22
Shield
PROFIBUS module
A
PROFIBUS DPV1 in / out signal
B
PROFIBUS DPV1 in / out signal
Note:
The system design is such that the entire bus connection will be
interrupted if you disconnect the PROFIBUS cable on the device. As
an alternative, please consider the version with DP M12 connection
socket (Section Fehler! Verweisquelle konnte nicht gefunden
werden.).
1) Note regarding terminating resistor: The bus
termination with jumpers should only be used if just the device is
connected to this PROFIBUS line.
The incoming and outgoing PROFIBUS cables are connected to
terminals A (green cable) and B (red cable) respectively. The other
terminal blocks must not be used (CAN bus, for internal use only).
For information regarding the PROFIBUS DP termination, refer to
Section 5.3.
Important (Notice)
To help ensure safe operation of the module and to minimize EMC interference, the cable
shield for the PROFIBUS lines must be attached to the relevant terminals in the terminal box.
A low-resistance ground must also be connected to the grounding screw for the box (M6
threads) (cable cross section of at least 4 mm
Important (Notice)
Disconnecting the PROFIBUS cable on the device interrupts the entire bus connection.
Device versions that can be disconnected without causing an interruption: See Section 5.3.
28 - EN
Cable shield
connected to
ground (PE)
by means of
capacitive
coupling
2
).
Sensyflow FMT500-IG
11
11
12
12
13
13
14
14
15
15
16
16
17
17
18
18
19
19
20
20
21
21
22
22
G00831
PROFIBUS
terminals A / B
Jumper for
PROFIBUS
terminating
resistor 1)
G00830
CI/FMT500-IG-X1