Pab Minimal Gas Adjustment - Ecoflam MAX GAS 350 P Manual De Instrucciones

Quemadores de gas de aire soplado
Ocultar thumbs Ver también para MAX GAS 350 P:
Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 38
420010563501 Max Gas 350 - 500 P/P AB
EN

PAB MINIMAL GAS ADJUSTMENT

AIR SERVOMOTOR ( SIEMENS SQN 75 ) MAX GAS 350-500 PAB
Remove cover to enter the adjusting cams. Adjust cams through the suitable key (on
issue) and a screwdriver.
I - Adjusting cam (BLUE) for air damper position on burner's shutdown
(total close 0°).
II - Adjusting cam (ORANGE) for opening position in ignition and Low Flame
(by the screwdriver).
III - Adjusting cam (RED) for opening position in High Flame (max. output).
IV - Adjusting cam (BLACK) to allow the opening of High flame solenoid valve.
20
3
D
E
T
A
L I
3

Hide quick links:

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Max gas 350 p abMax gas 500 pMax gas 500 p abMax gas 350 pr-mdMax gas 500 pr-md

Tabla de contenido