DESCRIPTION OF THE CONTROL PANEL OF THE BURNER
YEARLY INSPECTION
Periodic inspection of the burner (combustion head, electrodes, etc.) must be carried out by authorised personnel once
or twice a year, depending of use. Before carrying out maintenance inspection on the burner, it is advisable to check its
general condition and carry out the following operations:
- Disconnect the burner from the power supply (remove the plug).
- Close the gas cock.
- Remove the burner cover, clean the fan and air intake.
- Clean the combustion head and check the position of the electrodes.
- Re-assemble the parts.
- Check the seal on the gas pipe fittings.
- Check the flue.
- Restart the burner.
- Check the combustion parameters (CO
BEFORE EACH INTERVENTION CHECK;
- That the system is supplied with power and the burner connected.
- That the gas pressure is correct and the gas cock open.
- That the control systems are correctly connected.
If all these conditions are present, start the burner by pressing the release button. Check the burner cycle.
THE BURNER WILL NOT START;
- Check the switch, thermostats, motor, gas pressure.
THE BURNER PREVENTILATES AND LOCKS AT THE END OF THE CYCLE:
- Check the air pressure and fan.
- Check the air pressure switch.
THE BURNER PREVENTILATES AND WILL NOT IGNITE:
- Check the assembly and position of electrodes.
- Check the ignition cable.
- Check the ignition transformer.
- Check the safety devices.
THE BURNER STARTS UP AND LOCKS AFTER THE SAFETY TIME LIMIT:
- Check that the phase and neutral wires are correctly connected.
- Check the gas electrovalves.
- Check the position of the detection electrode and its connection.
- Check the detection electrode.
- Check the safety devices.
THE BURNER STARTS UP AND LOCKS AFTER RUNNING FOR A FEW MINUTES.
- Check the pressure regulator and the gas filter.
- Check the gas pressure with an ammeter.
- Check the detection value (min 1,5 µA Landis).
2
3
0
4
I
1

MAINTENANCE

= 9.5 to 9.8),(CO = less than 75 ppm)
2
420010563501 Max Gas 350 - 500 P/P AB
1 - reset key
2 - working lamp
3 - main switch I / O
4 - fuse
25