2.2

Residual hazards

{
Danger!
Dangerous electrical voltage
All power terminals remain live for up to three minutes after mains
disconnection.
Possible consequences:
ƒ
Protective measures:
ƒ
ƒ
O
Warnings!
Conditions of Acceptability:
ƒ
ƒ
ƒ
ƒ
ƒ
EDK94AZRS6 DE/EN/FR/ES/IT 7.0
Death or severe injuries when touching the power terminals.
Switch off the power supply and wait for at least three minutes
before working on the power terminals.
Make sure that all power terminals are deenergised.
The products covered by this report are only intended for use
with Power Conversion Equipment (inverters).
Consideration shall be given to the field wiring leads. No strain
relief test was performed on the leads.
The devices in this report are only evaluated for factory wiring
use.
Temperature tests were performed with hook mounted drive.
Reactor model E94AZR0544 shall be installed with input wiring
of 4 AWG minimum. Reactor model E94AZR0954 shall be
installed with input wiring of 1/0 AWG minimum.
l
Safety instructions
Residual hazards
2
31