BIG ASS FANS COLD FRONT 100 Manual De Operación Y Mantenimiento página 15

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

Spring cleaning
☑ Remove the cooling media and clean out any debris in the
water pan at the bottom of the cooler.
☑ Remove the distribution tube from the mounting clips.
Remove the plug at the end of the tube and flush out.
Clean the distribution holes with a small brush and flush
with water to verify all holes are clear.
☑ If the cooling media is heavily stained with minerals or is
damaged, replace the media. Replacement cooling media
is available at bigassfans.com. Verify the media is installed
correctly with the arrows on the side.
☑ Connect the water line and turn on the water supply.
Check the float valve and make sure it is operating
properly. Verify that the float valve is shutting the water off
before walking away.
☑ Switch on the fan motor and pump. Make sure the cooling
media is being evenly saturated with water. Small dry
streaks are acceptable.
Mid-summer checkup
☑ Make sure the float valve is working properly. If the valve
sticks, the water will run continuously and flood the
reservoir. If this occurs, install a new float valve or contact
Customer Service.
☑ Check all other working parts for cracks or damage,
including the pump, fan motor, and fan belt.
☑ Check the condition of the cooling media. The cooler runs
most efficiently when the media is clean. If the media has
a heavy accumulation of mineral deposits, replace it.
☑ Use the drain valve to empty the reservoir. Remove any
debris.
WWW.BIGASSFANS.COM
MAINTENANCE
© 2020 DELTA T LLC
ALL RIGHTS RESERVED.
13

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Cold front 200F-ev1-1001s75F-ev1-1001s75v60

Tabla de contenido