salmson LRE Serie Instalacion Y Puesta En Servicio página 104

Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

English
No.
Designation
5.7.2.0
Pressure value cor-
rection
5.7.5.0
Switching fre-
quency
5.7.6.0
SBM function
5.7.7.0
Factory setting
5.8.0.0
Other settings 2
5.8.1.0
Pump kick
5.8.1.1 Pump kick active/
inactive
5.8.1.2 Pump kick time
interval
94
Type
Symbol Values/explanations
Display orientation
±
When pressure value correction
is enabled, the differential pres-
sure deviation measured by the
differential pressure sensor that
is factory-fitted on the pump
flange is taken into account and
corrected.
Pressure value correction off
Pressure value correction on
HIGH
High switching frequency
(factory setting)
MID
Medium switch frequency
LOW
Low switching frequency
±
Setting for behaviour of signals
SBM run signal
SBM readiness signal
SBM mains on signal
±
OFF (default setting)
Settings are not changed by
confirming.
ON
Confirming will reset the set-
tings to factory settings.
Caution!
All manual settings will be lost.
ON (factory setting)
Pump kick is activated.
OFF
Pump kick is deactivated.
±
Can be set between 2 h and 72 h
in 1 h steps
Display conditions
Only displayed in p-c mode.
Is not displayed for all pump
variants.
Carry out the switch over/
change only when the pump
is at a standstill (not when
the motor is running)
Is not displayed when access
disable active.
Is not displayed when build-
ing management system
active
Is not displayed when access
disable active.
Is not displayed when build-
ing management system
active
For parameters that are
changed by a factory setting,
see chapter 13 "Factory set-
tings" on page 112.
Is not displayed if pump kick
is deactivated
Salmson 11/2017

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Jre serie

Tabla de contenido