4.0
Electrical Connections - Initial Setup / Raccordements électriques - Réglage initial /
Conexiones eléctricas / Configuración inicial
20mA
4mA
0mA
0%
Standard setting
4.1
20mA
12mA
4mA
0mA
100%
0%

Split range setting

4.2
Split range jumper
4.3
100%
20mA
12mA
4mA
0mA
0%
100%
Setting of second positioner
18
4.6
Split range setting
To change the range from full range to split range remove the
split range jumper.
This way the positioner can be controlled either by a 4 to 12mA
signal or a 12 to 20mA signal.
The start point can be set at 4 or 12mA with the "ZERO"-
trimmer. The end point (range) can be set at 12 or 20mA with
the "SPAN"-trimmer.
Note:
1. These two adjustments are interrelated, so the zero may
have to be reset after changing the range and vice
versa.
2. To increase the signal turn the trimmer screws clock-
wise (CW). To decrease the signal turn the trimmer
screws counter clockwise (CCW).
Standard setting =
Mise au point standard =
Configuración estándar
Split range setting =
Réglage de portée divisée =
Ajuste del rango dividido
Setting of second positioner =
Réglage de positionneur deuxième =
Ajuste del posicionador segundo
Split range jumper =
Cavalier de portée divisée =
Puente de rango dividido