EN
POSITION OF IGNITION ELECTRODES
For a correct burner ignition, carefully respect the dimensions shown by the picture.
3 ÷ 4 mm
5 ÷ 6 mm
CLEANING AND MAINTENANCE OF FILTERS MOUNTED ON THE PREHEATER
REMOVING OF THE FILTER
1. Switch-off the burner.
2. Loosen screw B and drain part of the fuel from the heater, until the fuel level drop below the filter.
3. Unscrew and pull out the stem filter A from its seat.
4. Clean the filter and reassemble the parts as shown by the picture, then fit it in its own seat.
It is advisable to replace all filter and valve gaskets whenever they are removed.
Note that when the burner is working the heater has a pressure of abt. 23 bar, and that it becomes very dangerous