LOADING OF DEFAULT
PARAMETERS
If necessary, it is possible to restore all the parameters to their
standard or default value (see table at the end)
WARNING: This procedure causes the loss of all the
customized parameters, therefore it has been put outside the
configuration menu, to reduce the possibility of executing it by
mistake.
1. Press and hold down the MENU key until the -dEF appears
on the display
2. Release the MENU key: the display will show ESC (press the
MENU key only if you want to leave this menu)
3. Press the DOWN key: dEF will appear on the display.
4. Press the MENU key: no will appear on the display.
5. Press the DOWN key: Si will appear on the display.
6. Press the MENU key: All of the parameters are returned to
their default values (see the table on pages 50-51) and the
display shows the control panel
SELF-LEARNING OF WORKING
TIMES
This menu allows the automatic learning of the times necessary
to open and close the gate.
During this phase, the control unit memorizes also the forces
necessary to open and close the gate: these values will be
activated by using the obstacle sensor.
The encoder positions are also saved, if enabled.
CAUTION: Before continuing, make certain that the
limit switch(es) and encoder(s) have been installed
correctly. Limit switches and encoders, if installed, must be
enabled using the specific menu.
1. Press and hold down the MENU key until the -APP appears on
the display
2. Release the MENU key: the display will show ESC (press the
MENU key only if you want to leave this menu)
3. Press the DOWN key: t.LAv will appear on the display.
4. Press the MENU key to start the self-learning cycle for the
work cycle times:
CAUTION: This procedure varies based on the number of gate
panels and travel control devices installed.
If there is no limit switch or encoder installed, only points 4.4
and 4.5 are performed. If there is only one motor (t.AP2 = 0),
the procedure starts from point 4.3
4.1
Gate panel 1 is opened for a few seconds
4.2
Gate panel 2 is closed until one of the following
conditions occurs:
- it reaches the limit switch
- The obstacle sensor or the encoder detect that the
gate panel is jammed
- A START command is given
This position is memorized as the close point for gate
panel 2.
4.3
Gate panel 1 is closed until one of the conditions listed
in point 4.2 occur:
This position is memorized as the close point for gate
panel 1.
4.4
Each gate panel is opened. The operation ends when
once of the conditions indicated in point 4.2 occur (the
first START stops gate panel 1, the second START stops
gate panel 2).
The time required is memorized as the open time.
4.5
Each gate panel is closed. The operation ends when one
of the conditions indicated in point 4.2 occurs or when
the closed position is reached.
The time required is memorized as the close time.
5. The display shows the value recommended for the obstacle
sensor of motor 1. If no operations are performed for
20 seconds, the controller exits the programming phase
without saving the recommended value.
6. The recommended value can be changed using the UP and
DOWN keys. Press the MENU key to confirm the value
displayed and the display will show SEn1
7. Press the DOWN key: The display will show SEn2. Press the
MENU key to display the recommended value for the obstacle
sensor for motor 2, which can be changed in a similar manner
as that for SEn1.
8. Hold down the DOWN key until the FinE appears on the
display, then press the MENU key, select Si and press the
MENU key to exit programming and save the values for the
sensors.
CAUTION: If the controller exits programming due to
time out (1 minute), the obstacle sensors return to the values
that were set prior to performing self-learning (according to the
default values, the sensors are disabled).
The open/close times and the encoder positions are always
saved.