Output module CPX-2AA-U-I
(cont.)
Actuator supply
– Loading capacity
– Fuses
– Response current
– Reaction after end of overload
– Protection against incorrect
polarity 24 V actuator supply
– Protection against reverse
voltage
– Electrical isolation
– Between channel and 24 V
– Between the channels
Festo CPX-AX 0206NH English
Voltage
Current
outputs
outputs
24 V
, one connection per
OUT
output, the same supply
potential at all outputs
Max. sum continuous current
per module 2.8 A
Electronic, thermal
4...10 A
Can be parametrized
(see parameters)
Yes
Max. 30 V
The logic supply for the electri-
cally isolated analogue part is
branched from the analogue
voltage
Yes (no potential isolation if
OUT
internal sensor supply is used)
No
25