4
Technical specifications
Inut module CPX-2AE-U-I
General technical specifica-
tions of the CPX terminal
Protection class as per
EN 60529
Operating voltage supply
– Rated voltage
– Internal current consump-
tion at 24 V (internal
electronics)
Analogue inputs
– Channels
– Input ranges
– Cable length
– Resolution
– Isolation voltage
– Potential connection
– Analoge value formation
– Permitted potential
differences
– Between input channels
– Between inputs and FE
Festo CPX-AX 0206NH English
Voltage inputs
Current inputs
See CPX system manual
See technical specifications of the fitted
sub-base
V
(electronics/sensors)
EL/SEN
24 V DC ± 25 %
Typ. 50 mA
Total of 2 input channels per module
Max. 2 channels
Max. 2 channels
0...10 V
0...20 mA/4...20 mA
Max. 30 m, screened
12 bits (A-D converter, internal)
500 V DC
High ohm + capacitive connection to FE
Measuring principle succesive
approximation, conversion time per
channel typ. 70 µs,
module cycle time ≤ 2.5 ms
AC 1 Vpp
0 V AC
30 V DC
30 V DC
21