TL100
PROTECTION FUSES
Position
Value
F1
500 mA
F2
160 mA
SETTINGS (DIP SWITCH - Sw1)
DIP
Status
Function
ON
Selects the operating mode with detection devices
DIP 1
OFF
Selects the time-based operating mode
ON
Configures the input IN_1 as N.C.
DIP 2
OFF
Configures the input IN_1 as N.O.
ON
Configures the input IN_2 as N.C.
DIP 3
OFF
Configures the input IN_2 as N.O.
ON
DIP
Not used
4 - 5 - 6
OFF
JUMPER
J2
CLOSED
J3
CLOSED
NOTE to be used if the lights are powered directly from the control unit. (2)
TRIMMERS
Position
Description
Adjusts the time both red lights stay on to between 5 and 120 s.
TR1
Turn the trimmer clockwise to increase the time.
Adjusts the time the green light stays on to between 5 and 120 s.
TR2
Turn the trimmer clockwise to increase the time.
TR3
Adjusts the priority time to between 5 and 120 s. Turn the trimmer clockwise to increase the time.
OPERATION
1.1. TIME-BASED OPERATING MODE (DIP 1 OFF)
At power on the control unit sets both red lights and tests the limit switch input. As long as the limit switch input
remains closed, the operating cycle is locked and the lights stay red.
When the limit switch input opens (gate open), the cycle as described below starts:
1. both lights stay red for the time T1, adjustable with the relative trimmer TR1;
2. when T1 has elapsed, the light connected to terminals "1" turns green for the time T2, adjustable with the relative
trimmer TR2, while the one connected to terminals "2" stays red.
3. when T2 has elapsed, both lights turn red again for the time T1 in order to free the passage;
Type
Description
24 VAC output protection
FAST
Board protection
FAST
Connects terminal 4 to terminal 11
Connects terminal 4 to terminal 14