Descargar Imprimir esta página

SFA Sanicondens Plus Instrucciones De Instalación página 6

Ocultar thumbs Ver también para Sanicondens Plus:

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 12
UK
1
CAUTION
SANICONDENS
®
Plus is a pump for lifting condensation
water from an air conditioning system, a condensation boiler
or from refrigeration units. Include a neutralisation device if
necessary (see the manufacturer's instructions for your boiler).
The pump starts automatically and has a high level of
performance, safety and reliability provided that all the
installation and maintenance instructions described in this
notice are strictly followed.
Please take particular note of the information marked by :
«
» Indication that a risk of electrical origin exists,
«
» Instructions for use only by qualified professionals.
OPERATING PRINCIPLE
SANICONDENS
®
Plus contains a pump. The tank of the
SANICONDENS
Plus is fitted with a float which controls the
®
operation of the motor. When the condensates enter the tank,
the pump starts up.
2
LIST OF DOCUMENTS PROVIDED: see fig.2
3
DIMENSIONS: see fig.3
4
SANICONDENS
Plus AREA OF APPLICATION AND
®
TECHNICAL DATA
Air conditioning systems, boilers,
Application
Type
Max. vertical pumping
Maximum flow rate (litres / hour)
Flow rate at 4 m
Min. pH
Voltage
Frequency
Power rating
Current consumption
Electrical class
Protection index
Sound level
Average utilisation temperature
Maximum allowable temperature
Net weight
Dimensions
Tank volume
Supply cable
Discharge hose
Alarm cable (3 core)
Wall fastening
CAUTION:
All applications other than those described in this notice are
prohibited.
5
PERFORMANCE CURVES: see fig.5
6
VERTICAL PUMPING/HORIZONTAL PUMPING:
see fig.6
10721 140 SANICONDENS PLUS.indd 6
refrigeration units
CD10
4,5 m
342
156
2,5
220-240 V
50 Hz
60 W
0,52 A
I
IP20
< 45 dBA
35°
80°
S3 15% (90s ON, 510s OFF)
2000 g
301x160x146 mm
2,1 litre
2 m
6 m
2 m
Yes
7
INSTALLATION
SANICONDENS
Plus has wall fixings.
®
The unit should be easy to access for testing and
maintenance.
The unit must be installed level. Adjust the installa-
tion using a spirit level before fixing the unit.
Make sure that the equipment is protected from damp while
installing it.
7a
CONNECTION AT THE COVER INLET
The unit has 4 inlets 28 mm in diameter (2 on each side - see
7a
1 ). To connect the water to be drained off, connect
fig.
the water inlet to one of the inlets and close off any unused
D
inlets with the plugs
. If necessary, use the rubber adaptator
X
7a
19, 32, 40 mm (see fig.
7b
CONNECTING TO THE DISCHARGE PIPE
The SANICONDENS
Plus discharge pipe must be connected
®
A
to the flexible hose
(supplied : length 6 m). This hose should
be used to form the vertical section of the discharge pipe.
‡ 3ODFH WKH IOH[LEOH KRVH RQWR WKH QRQUHWXUQ YDOYH RI WKH
SANICONDENS
Plus (see diagram
®
‡ 3RVLWLRQ WKH IOH[LEOH KRVH LQ WKH
most vertical position
possible to avoid it kinking.
‡ ,W LV DGYLVDEOH WR PDNH D VPRRWK EHQG WR DYRLG WKH KRVH
kinking.
‡ The hose has a diameter of less than 8 mm and can be
connected to a PVC hose of larger diameter by a plastic
reducing connection on the horizontal section of the dis-
charge hose, or connected to your drain by a plastic redu-
Y
cing connection
. In UK fittings such as Speedfit from
John Guest are available -part numbers PEM202215W
used with PEM06150W to connect to 22mm pipework.
The SANICONDENS
®
Plus is fitted with a non-return valve
to prevent re-activation.
INSTRUCTIONS INTENDED SOLELY FOR
QUALIFIED PROFESSIONALS
7c
ELECTRICAL CONNECTION
The electrical installation should be carried by a qualified person.
The unit should be connected to a fully earthed electrical
supply. All wiring must conform to BS7671, 1992 require-
ments for electrical installations. The SANICONDENS
requires a 220/240V single phase AC 50 Hz supply (UK
specification). Do not connect SANICONDENS
conventional plug and socket. It must be wired into a fused,
unswitched, fixed wiring connector fitted with a 5 amp fuse.
SANICONDENS
®
Plus has an Earth wire. The wires in the
mains lead are
coloured in accordance with the following code:
Brown – Live
Blue – Neutral
Warning:
Ensure the electricity is turned OFF at the main
switch board before wiring to connector.
All work on cable, pressure chamber and motor should only
be carried out by a qualified Saniflo servicing agent, as
special tools are required.
INSTRUCTIONS INTENDED SOLELY FOR
QUALIFIED PROFESSIONALS
7d
ALARM
SANICONDENS
Plus is fitted with a detection system
®
that can trigger an alarm if the water level rises too high
(audible or visual alarm, 1.5V to 230V), see diagram
1
. Brown wire: shared wire
2
. Black wire: normally off
3
. Blue wire: normally on
To fit the alarm, connect the blue and brown wires
of the alarm to the respective terminals on the
SANICONDENS
®
Plus.
2 ).
) .
7b
Plus
®
Plus to a
®
Green/Yellow – Earth
:
7d
23/10/12 14:17

Publicidad

loading