NOTE: When turning the LUX control (starting from the moon symbol),
if the current ambient light value is reached, the red LED will light up
(as a setting aid). The LED will automatically go out after 30 seconds.
: "short pulse" function for light channels C1
Once the detector has been triggered by movement (lighting is
below preset ambient lighting level), the lighting and the red LED
will be switched on for 1 second and then off for 9 seconds.
: "short pulse" function for channel C2 (HVAC)
Once the detector has been triggered by movement, the channel
and the green LED will be switched on for 5 seconds and then off
for 5 seconds.
Field of detection "test" function
The connected lighting is switched on – immediate, load-free indication
of movement given by 2 short flashes of the blue LED (blue mode).
DIP switch 2: fully automatic (A)/semi-automatic (M)
DIP switch 2 is only active if DIP switch 1 has been switched to manual!
Whichever option you choose affects both C1 and C2. For a detailed
description of fully automatic/semi-automatic mode, please refer to
chapter 7 "Functions".
DIP switch 3: Standard/corridor function:
ON/OFF = standard function
The lighting can also be switched on and offf using an external button.
ON = corridor function
The lighting can only be switched on using an external button.
DIP switch 4: Adjusting the sensitivity
The device is set to maximum sensitivity "S-max." in the factory settings.
If the switch is set to "S-min.", the level of sensitivity is reduced.
This setting is recommended if undesired switching occurs due to
interference sources, such as hot air streams.
7 • FUNCTIONS
Fully automatic mode
Light channel C1 will switch on automatically, depending on the preset
light value and detection of movement. This will remain on for as long
as movement is detected and as long as the ambient light value does
not exceed the preset light value. The HVAC channel is switched on when
movement is detected, regardless of the ambient light value. The time
settings for the respective channels will start if movement is no longer
detected. Each channel can also be manually switched on or off using
buttons S1 – S2. The device is preset to fully automatic mode.
Semi-automatic mode for light channel C1
Switched ON/OFF manually using the S1 button. They will remain on for
as long as movement is detected and as long as the ambient light value
does not exceed the preset light value.
Semi-automatic mode for HVAC channel
Switched ON/OFF using the S2 button. If movement is no longer detected,
the time setting for C2 will start and the lighting will switch off once the
set time has elapsed.
ECO semi-automatic mode for light channel C1
Light is switched on manually using the S1 button, no automatic activation.
GB
15