17.4 Set manual speed
Pump variant
TPE3, TPE3 D
TPE2, TPE2 D
This menu is only available in the advanced control panel. With
Grundfos GO, you set the speed via the Setpoint menu.
You can set the pump speed in % of the maximum speed. When
you have set the operating mode to Manual, the pump starts
running at the set speed. The speed can then be changed
manually via Grundfos GO or via the advanced control panel.
Factory setting
See section
35. Factory
settings.
17.5 "Set user-defined speed"
You can set the motor speed in % of the maximum speed. When
you have set the operating mode to "User-defined speed", the
motor runs at the set speed.
17.6 Control mode
Pump variant
TPE3, TPE3 D
TPE2, TPE2 D
Possible control modes:
•
AUTO
ADAPT
•
FLOW
ADAPT
•
Prop. press. (proportional pressure)
•
Const. pressure (constant pressure)
•
Const. temp. (constant temperature)
•
Con. diff. press. (constant differential pressure)
•
Con. diff. temp. (constant differential temperature)
•
Const. flow rate (constant flow rate)
•
Const. level (constant level)
•
Const. other val. (constant other value)
•
Const. curve (constant curve).
Set the operating mode to Normal before you enable
a control mode.
You can change the setpoint for all control modes, except
AUTO
and FLOW
, in the Setpoint submenu under
ADAPT
ADAPT
Settings when you have selected the desired control mode.
Factory setting
See section
35. Factory
settings.
32
Set manual speed
●
●
"Control mode"
●
●
17.6.1 AUTO
ADAPT
Pump variant
TPE3, TPE3 D
TPE2, TPE2 D
The AUTO
control mode continuously adapts the pump
ADAPT
performance according to the actual system characteristic.
Manual setting of the setpoint is not possible.
H
H
fac
A
1
H
auto_min
A
3
Fig. 35 AUTO
ADAPT
When the AUTO
control mode has been enabled, the pump
ADAPT
will start with the factory setting, H
adjust its performance to A
. See fig. 35.
1
When the pump registers a lower head on the maximum curve,
A
, the AUTO
function automatically selects a
2
ADAPT
correspondingly lower control curve, H
system close, the pump will adjust its performance to A
A
:
Original duty point.
1
A
:
Lower registered head on the maximum curve.
2
A
:
New duty point after AUTO
3
H
:
Original setpoint setting.
set1
H
:
New setpoint after AUTO
set2
H
:
Factory setting.
fac.
H
: A fixed value of 5 ft (1.5 m).
auto_min
The AUTO
control mode is a form of proportional-pressure
ADAPT
control where the control curves have a fixed origin, H
The AUTO
control is developed specifically for heating
ADAPT
systems and we do not recommend that you use it for
air-conditioning and cooling systems.
"AUTO
"
ADAPT
●
-
H
set1
H
set2
A
2
Q
is equal to H
, and then
fac
set1
. If the valves in the
set2
.
3
control.
ADAPT
control.
ADAPT
.
auto_min