Analog Output; Controller"("Controller Settings") - Grundfos TPE2 D Manual Del Usuario

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

17.17 Analog output

Pump variant
TPE3, TPE3 D
TPE2, TPE2 D
Function

Analog output

* See section
9.5.1 Connection terminals, advanced functional
module, FM
300.
The analog output enables the transfer of certain operating data
to external control systems.
To set up the analog output, make the settings below.
Output signal
0-10 V
0-20 mA
4-20 mA.
Function of analog output
Actual speed
Signal range
[V, mA]
0
0-10 V
0 V
0-20 mA
0 mA
4-20 mA
4 mA
The reading is a percentage of nominal speed.
Actual value
Signal range
[V, mA]
Sensor
0-10 V
0 V
0-20 mA
0 mA
4-20 mA
4 mA
The reading is a percentage of the range between sensor
sensor
.
max
Resulting setpoint
Signal range
[V, mA]
0
0-10 V
0 V
0-20 mA
0 mA
4-20 mA
4 mA
The reading is a percentage of the external setpoint range.
Motor load
Signal range
[V, mA]
0
0-10 V
0 V
0-20 mA
0 mA
4-20 mA
4 mA
Analog output
Terminal*
12
Actual speed
[%]
100
200
5 V
10 V
10 mA
20 mA
12 mA
20 mA
Actual value
Sensor
min
max
10 V
20 mA
20 mA
and
min
Resulting setpoint
[%]
100
10 V
20 mA
20 mA
Motor load
[%]
100
10 V
20 mA
20 mA
The reading is a percentage of the range between 0 and 200 % of
the maximum permissible load at the actual speed.
Motor current
Signal range
[V, mA]
0
0-10 V
0 V
0-20 mA
0 mA
4-20 mA
4 mA
The reading is a percentage of the range between 0 and 200 % of
the rated current (I
).
N
Limit 1 exceeded and Limit 2 exceeded
Limit-exceeded function
Signal range
[V, mA]
Output not active
0-10 V
0 V
0-20 mA
0 mA
4-20 mA
4 mA
The Limit-exceeded function is typically used for monitoring of
secondary parameters in the system. If the limit is exceeded, an
output, warning or alarm is activated.
Flow rate
Signal range
[V, mA]
0
0-10 V
0 V
0-20 mA
0 mA
4-20 mA
4 mA
The reading is a percentage of the range between 0 and 200 % of
the nominal flow.
Factory setting
See section
35. Factory
settings.

17.18 "Controller"("Controller settings")

Pump variant
TPE3,TPE3 D
TPE2,TPE2 D
The pumps have a factory default setting of gain, K
time, T
.
i
However, if the factory setting is not the optimum setting, you can
change the gain and the integral time:
Set the gain within the range from 0.1 to 20.
Set the integral time within the range from 0.1 to 3600 s.
If you select 3600 seconds, the controller functions as a
P controller.
Furthermore, you can set the controller to inverse control.
This means that if the setpoint is increased, the speed is reduced.
In the case of inverse control, set the gain within the range from
-0.1 to -20.
Motor current
[%]
100
200
5 V
10 V
10 mA
20 mA
12 mA
20 mA
Output active
10 V
20 mA
20 mA
Flow rate
[%]
100
200
5 V
10 V
10 mA
20 mA
12 mA
20 mA
"Controller" ("Controller
settings")
and integral
p
43

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Tpe3 d

Tabla de contenido