Descargar Imprimir esta página

Johnson Controls YORK VCH-20 Instrucciones De Instalación página 6

Ocultar thumbs Ver también para YORK VCH-20:

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 1
Vertical air discharge for
VCH - 45, 60, 75 and 90A
This accessory allows changing the stand-
ard horizontal air discharge, on the VCH 45A
to 90A outdoor units, to a vertical discharge,
and the process is as follows:
1.- Remove and discard the top panel 1
and the grids 2 (Fig. 1).
2.- Remove both fan, mounted as standard
General dimensions mm.
Model
E
VCH 45A and 60A
781
VCH 75A and 90A
898
All data subject to change without notice.
6
on support "A" (Fig. 2).
3.- Change the motors and their supports,
the fastening rods and screws to the B
position in the 8 Ø holes drilled on the
fan as indicated, being careful to leave
the pulleys aligned (the tensing centre
should be at about 20 mm. from the front
of the fan) (Fig. 3).
4.- Fasten the fan to tabs "C" and supports
"D" of the top panel 3 , either before or
Fig. 1
Fig. 4
F
G
2 240
394
1 990
2 660
394
2 410
H
I
J
281
479
45
475
GB
after installing same on the machine,
with the new self threading screws in-
cluded in the kit (Fig. 3).
5.- Install the top panel 3 and the plenum
cover 4 (Fig. 4).
6.- If the unit is to operate without ducts,
install the protection grids included with
the kit at the mouths of the fans (self
threading screws are supplied for this
assembly).
������������������
�����������������
Fig. 2
Fig. 3
K
L
562
439
759
500
M
N
21
408
30
412

Publicidad

loading