Table 8.2: Other Regions
Rated Current of Nominal Cross-Sectional
Appliance (A)
≤6
6 - 10
10 - 16
16 - 25
25- 32
32 - 45
b. Using wire strippers, strip the rubber jacket
from both ends of signal cable to reveal
about 15cm (5.9") of the wires inside.
c. Strip the insulation from the ends of the
wires.
d. Using a wire crimper, crimp u-lugs on the
ends of the wires.
NOTE: While connecting the wires, please
strictly follow the wiring diagram (found inside
the electrical box cover).
2. Remove the electric cover of the outdoor unit.
If there is no cover on the outdoor unit,
disassemble the bolts from the maintenance
board and remove the protection board.
(See Fig. 8.1)
Fig. 8.1
3. Connect the u-lugs to the terminals
Match the wire colors/labels with the labels on
the terminal block, and firmly screw the u-lug
of each wire to its corresponding terminal.
4. Clamp down the cable with designated cable
clamp.
Page 16
Area (mm²)
0.75
1
1.5
2.5
4
6
Cover
Screw
5. Insulate unused wires with electrical tape.
Keep them away from any electrical or metal
parts.
6. Reinstall the cover of the electric control box.
Harmonic declaration
"The equipment M4OB-36HFN8-Q complies with
IEC 61000-3-12 provided that the short-circuit
power Ssc is greater than or equal to 4787737.5
at the interface point between the user's supply
and the public system. It is the responsibility of
the installer or user of the equipment to ensure,
by consultation with the distribution network
operator if necessary, that the equipment is con-
nected only to a supply with a short-circuit power
Ssc greater than or equal to 4787737.5."
"The equipment M5OD-42HFN8-Q complies with
IEC 61000-3-12 provided that the short-circuit
power Ssc is greater than or equal to 3190042.5
at the interface point between the user's supply
and the public system. It is the responsibility of
the installer or user of the equipment to ensure,
by consultation with the distribution network
operator if necessary, that the equipment is con-
nected only to a supply with a short-circuit power
Ssc greater than or equal to 3190042.5."