2.3 CONNECTION PLUGS
2.3.1 120 VAC DUPLEX RECEPTACLE
This is a 120 Volt outlet protected against overload by a 14 Amp circuit
breaker (Figure 7). 14 Amps of current may be drawn from each socket,
however, total power drawn must be kept within data plate ratings. Use only
high quality, well insulated, 3-wire grounded cord sets rated for 125 Volts at
20 Amps (or greater).
2.3.2 120/240 VAC, 20A TWISTLOCK RECEPTACLE
This is a 120/240 Volt outlet protected against overload by a 14 Amp
circuit breaker (Figure 8). Connect a suitable 4-wire grounded cord
set to the plug and to the desired load. The cord set should be rated
for 250 volts at 20 amps (or greater) if the 120/240 receptacle is used
along with 120 volt receptacle. The total load drawn must not exceed
the data label ratings.
Figure 8 - 120 VAC Duplex & 120/240 VAC Twistlock
IMPORTANT: Do not overload the generator. Also, do not overload
individual panel receptacles. These outlets are protected against
overload with circuit breakers. If amperage rating of any circuit
breaker is exceeded, that breaker opens and electrical output to that
receptacle is lost. Read "Don't Overload the Generator" carefully.
2.4 HOW TO USE THE GENERATOR
If there are any problems operating the generator, please call the
generator helpline at 1-888-436-3722.
Never operate in an enclosed area or indoors! NEVER
use in the home, in a vehicle, or in partly enclosed areas
such as garages, EVEN IF doors and windows are open!
ONLY use outdoors and far from open windows, doors,
vents, and in an area that will not accumulate deadly
exhaust.
The engine exhaust fumes contain carbon monoxide,
which can you cannot see or smell. This poisonous
gas, if breathed in sufficient concentrations, can cause
unconsciousness or even death.
Adequate, unobstructed flow of cooling and ventilating
air is critical to correct generator operation. Do not
alter the installation or permit even partial blockage of
ventilation provisions, as this can seriously affect safe
operation of the generator. The generator MUST be
operated outdoors.
This exhaust system must be properly maintained. Do
nothing that might render the exhaust system unsafe or
in noncompliance with any local codes and/or standards.
Always use a battery operated carbon monoxide alarm
indoors, installed according to the manufacturer's
instructions.
2.4.1 GROUNDING THE GENERATOR WHEN USED AS A
PORTABLE
This generator has an equipment ground that connects the generator
frame components to the ground terminals on the AC output
receptacles (see NEC 250.34 (A) for explanation). This allows the
generator to be used as a portable without grounding the frame of the
generator as specified in NEC 250.34.
Special Requirements
There may be Federal or State Occupational Safety and Health
Administration (OSHA) regulations, local codes, or ordinances that
apply to the intended use of the generator.
Please consult a qualified electrician, electrical inspector, or the local
agency having jurisdiction:
• In some areas, generators are required to be registered with local
utility companies.
• If the generator is used at a construction site, there may be
additional regulations which must be observed.
Operation
7