Relay outputs
Connections
Case
Assembly
Display
Keypad
Infrared receiver
Clock with backup battery
Buzzer
Clock
Operating temperature
Operating humidity
Storage temperature
Storage humidity
Front panel index of
protection
Environmental pollution
PTI of insulating materials
Period of stress across the
insulating parts
EN60730-1
250 V~
8 A
8 (4) A on N.O.
6 (4) A on N.C.
2 (2) A on N.C. e N.O.
16 A
1 0 (4) A up to a 60 °C on N.O.
12 (2) A on N.O. and N.C.
2 Hp
10 (10) A
30 A
12 (10) A
insulation from the very low voltage parts
insulation between the independent relay outputs
Type of connection
fi xed screw
plug-in for screw blocks
spade with crimped contact
wire cross-section for probes and
digital inputs
wire cross-section for power supply
and loads
The correct sizing of the power and connection cables between the instrument and the loads is the responsibility of
the installer.
In the max load and max operating temp. conditions, the cables used must be suitable for operation up to 105 °C.
plastic
bare board and front panel
wall mounting (with plastic case)
panel (with plastic front panel)
panel (bare board)
digits
display
operating status
8 mechanical buttons, keypad made in the polycarbonate label applied to the plastic case
available according to the model
available according to the model
available on all models
error at 25°C
error in the temperature range –10T60°C
ageing
discharge time
recharge time
bare board
with plastic case and following current confi gurations:
Relay 1, 12 A; Relay 2, 0 A; Relay 3, 4 A; Relay 4, 4 A; Relay 5, 4 A
Relay 1, 0 A; Relay 2, 12 A; Relay 3, 4 A; Relay 4, 4 A; Relay 5, 4 A
the currents indicated above are reduced according to the relays used
bare board
with plastic case
-20T70 °C
<90% rH non-condensing
with plastic case
panel installation
normal
> 250 V
long
according to the model
operating
cycles
100000
8 A resistive 2 FLA 12 LRA C 300
100000
12 A resistive 5 FLA 30 LRA C 300
100000
12 A resistive, 12FLA, 72 LRA
100000
12 A resistive, 2HP, 12 FLA
reinforced
6 mm in air, 8 on surface
3750 V insulation
basic
3 mm in air, 4 on surface
1250 V insulation
Cross-section
per cables from 0.5 a 2.5 mm
2
from 0.5 to 2.5 mm
(from 20 to 13 AWG)
from 1.5 to 2.5 mm
2
(from 15 to 13 AWG)
dimensions 200 x 240 x 93 mm
base dimensions 178 x 86 x 40 mm
front dimensions 100 x 90 x 12 mm
using fastening screws
using fastening screws
using fastening screws for base board
using fastening screws for front board
3 digit LED
from -99 to 999
indicated with LEDs and graphic icons made in the polycarbonate
label applied to the plastic case
± 10 ppm (±5.3 min/year)
- 50 ppm (-27 min/year)
< ±5 ppm (±2.7min/year)
typically 6 months (8 months maximum)
typically 5 hours (<8 hours maximum)
23
+050004105 rel. 0.0 del 27.07.05 - Preliminary version
UL 873
250 V~
Maximum current
2
12 A
spacing 162.5 x 218.5
spacing 159.5 x197.5
-10T65°C
-10T50°C
<90% rH non-condensing
IP65 without disconnecting switch
IP54 with disconnecting switch
IP54 with disconnecting switch
operating
cycles
30000
30000
30000