Power Terminals - Siemens SIMOVERT MASTERDRIVES 6SE7087-6CX87-2DA1 Manual Del Usuario

Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

05.2009
3.4

Power terminals

Siemens AG
6SE7087-6CX87-2DA1
SIMOVERT MASTERDRIVES
Cross-section S of DC link line
S ≤ 16 mm
2
2
< S ≤ 35 mm
2
16 mm
2
S > 35 mm
PE conductor cross-section must, however, be at least larger than
NOTE:
2
2.5 mm
.
Table 3-1
Connection cross-section of the PE conductor of the 5 – 200 kW
(DIN EN 61800-5-1)
Braking Unit
Mounting, Connecting-Up
Minimum cross-section MS of the
external PE conductor
MS ≥ S
MS ≥ 16 mm
2
MS ≥ S/2
3-7

Publicidad

Tabla de contenido
loading

Tabla de contenido