overload
utility power present
1c flashing
1g on
1 beep every second
Pulsar switches off automatically after
operating in overload for approximately
5 min.
no utility power present
1c flashing
1g on
1 beep every second
Pulsar switches off automatically after a
length of time which depends on the level
of overload.
NB:
Overload occurs if the load consumption of
the applications connected is greater than
the rated power of Pulsar.
To acknowledge the fault, push button 3 ,
temporarily disconnected Pulsar from the
wall socket (flex 5 ), disconnect non-
priority applications and re-start Pulsar.
MGE UPS SYSTEMS
operating anomalies
device fault
1b flashing
1g on
1 beep every second
v v v v v switch off Pulsar (push button 3 ),
disconnect from the wall socket (flex 5 ),
and check that Pulsar has not short-circuited
(disconnect all applications),
v v v v v check the input fuse 6b and replace it with
a fuse of the same rating or reset thermal
breaker 6 ,
v v v v v re-start Pulsar.
utility power outside limits
1a to 1g off
continuous beep
...
after the start-up sequence, if the audio
warning device sounds continuously, check
the voltage and frequency of your utility
power (see the § entitled "characteristics")
and/or recharge your battery for 8 hours.
Pulsar ESV +: E-51032616XT/AA
battery fault
A battery test is carried out while Pulsar, is in
start-up phase, then automatically every 7 days
(overhaul times adjustable using ESV Driver).
If a battery fault is detected, the following
occurs:
1a flashing
1g on
1 beep every second
recharge your battery for 8 hours.
If battery fault persists, see next page.
Start/Stop control on onput
receptacles 1 and 2 (PowerShare)
You can use the applications included on the
CD-ROM to remote control the Start/Stop
sequences on output receptacles 7a (or 7b)
is stopped, front panel led 1f (or 1e )
flashes, with 1 beep every second, beep can
be deactivated by "function" button 2 .
NB:
If the previous symptoms persist, contact our
after sales department.
27