Optional Heat Reclaim Module; Diagnostics - Troubleshooting; General; Displaying Alarms - Carrier AQUASNAP 30RB Manual De Controles Y Soluciones De Defectos

100 a 300
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

In the event of a communication fault between the two
units, each shall return to an autonomous operating mode
until the fault is cleared. If the master unit is halted due to
an alarm, the slave unit is authorised to start without prior
conditions.

5.15 - OPTIONAL HEAT RECLAIM MODULE

This option requires the installation of an additional board.
This board allows control of:
-
A heat reclaim condenser pump,
-
A heat reclaim condenser heater,
-
Two solenoid valves to shut off the heat reclaim coil
(one for each circuit),
-
Two solenoid drain valves for the heat reclaim coil (one
for each circuit),
-
Two solenoid valves to shut off the water condenser
(one for each circuit),
-
Two solenoid drain valves for the water condenser
(one for each circuit).
Selecting the heat reclaim mode can be done with either
the local interface or remotely with the (recl_sw) contact
or by CCN.
The heat reclaim function is active when: the heat reclaim
entering water temperature is lower than the heat reclaim
setpoint, minus half of the heat reclaim dead band.
The heat reclaim function is not active when: the heat
reclaim entering water temperature is higher than the heat
reclaim setpoint, plus half of the heat reclaim dead band.
In the dead band the function remains in its active mode.
The default value of the dead band is 4.4°C. This value can
be modifi ed by Carrier Service.
Changeover procedure from cooling mode to heat reclaim
mode:
-
Start-up of the condenser pump.
-
Verification of the condenser flow switch control
contact. If this remains open after one minute of
condenser pump operation, the circuit remains in
cooling mode and an alarm will be activated.
-
As soon as the saturated condensing temperature
reaches 30°C, the pumpdown sequence is activated.
-
Pumpdown: opening of the condenser water inlet valve
and closing of the air condenser air valves 3 seconds
later.
-
After one minute or when the subcooling value is above
-10°C the heat reclaim function is effective.

6 - DIAGNOSTICS - TROUBLESHOOTING

6.1 - GENERAL

The PRO-DIALOG Plus control system has many fault
tracing aid functions. The local interface and its various
menus give access to all unit operating conditions. If an
operating fault is detected, an alarm is activated and an
alarm code is stored in the Alarm menu.

6.2 - DISPLAYING ALARMS

The alarm LEDs on the summary interface (see section
4.1) give a quick display of the status of each circuit and
the unit as a whole.
A fl ashing LED shows that the circuit is operating but
there is an alarm.
A steady LED shows that the circuit has been shut
down due to a fault.
The Alarm menu on the main interface displays up to 5
fault codes that are active on the unit.

6.3 - RESETTING ALARMS

When the cause of the alarm has been corrected the alarm
can be reset, depending on the type, either automatically
on return to normal, or manually when action has been
taken on the unit. Alarms can be reset even if the unit is
running.
This means that an alarm can be reset without stopping
the machine. In the event of a power supply interrupt, the
unit restarts automatically without the need for an external
command. However, any faults active when the supply is
interrupted are saved and may in certain cases prevent a
circuit or a unit from restarting.
A manual reset must be run from the main interface using
the following procedure:
RESET OF ACTIVE ALARMS
OPERATION
ITEM NUMBER
2-DIGIT DISPLAY 4-DIGIT DISPLAY BUTTON LED
Hold down the MENU
button until the LED for
alarms lights. The 4-
0
digit display shows the
number of active
alarms (2 in this
0
example).
Press the Enter button
0
until "rESEt ALARrM" is
shown in the 4-digit
display.
Press the Enter button
0
again to validate the
reset. "Good" is
displayed for 2 seconds
then, "2 ALArM" and
then, "no ALArM".
ITEM VALUE
PRESS
MENU
2 ALArM
rESEt ALArM
Good
then, 2 AL
then, no ALArM
105

Hide quick links:

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Aquasnap 30rsAquasnap 30rb100Aquasnap 30rb300

Tabla de contenido